page 16 — DCa45SSIU4 60 hz generator • operatIon anD partS manUal — rev. #1 (10/24/13)
GENERATOR
The MQ Power Model DCA45SSIU4 generator (Figure 3) is
a high quality portable (requires a trailer for transport) power
source for telecom sites, lighting facilities, power tools,
submersible pumps and other industrial and construction
machinery.
engIne operatIng panel
The “Engine Operating Panel” is provided with the following:
Tachometer
Water Temperature Gauge
Warning Lamp
Pre-Heat Lamp
Oil Pressure Gauge
Charging Ammeter Gauge
Fuel Level Gauge
Panel Light/Panel Light Switch
ECU Controller
Engine Speed Switch
generator Control panel
The “Generator Control Panel” is provided with the following:
Frequency Meter (Hz)
AC Ammeter (Amps)
AC Voltmeter (Volts)
Ammeter Change-Over Switch
Voltmeter Change-Over Switch
Voltage Regulator
3-Pole, 110 amp Main Circuit Breaker
“Control Box” (located behind the Gen. Control Panel)
•
Automatic Voltage Regulator
•
Current Transformer
•
Over-Current Relay
•
Starter Relay
•
Voltage Selector Switch
oUtpUt termInal panel
The “Output Terminal Panel” is provided with the following:
Three 120/240V output receptacles (CS-6369), 50A
Three auxiliary circuit breakers, 50A
Two 120V output receptacles (GFCI), 20A
Two GFCI circuit breakers, 20A
Five output terminal lugs (3Ø power)
open Delta exCItatIon SYStem
The DCA45SSIU4 generator is equipped with the state of
the art
“Open-Delta”
excitation system. The open delta
system consist of an electrically independent winding
wound among stationary windings of the AC output
section.
There are four connections of the open delta A, B, C and
D. During steady state loads, the power from the voltage
regulator is supplied from the parallel connections of A to
B, A to D, and C to D. These three phases of the voltage
input to the voltage regulator are then rectified and are the
excitation current for the exciter section.
When a heavy load, such as a motor starting or a short
circuit occurs, the automatic voltage regulator (AVR)
switches the configuration of the open delta to the series
connection of B to C. This has the effect of adding the
voltages of each phase to provide higher excitation to the
exciter section and thus better voltage response during the
application of heavy loads.
The connections of the AVR to the AC output windings are
for sensing only. No power is required from these windings.
The open-delta design provides virtually unlimited excitation
current, offering maximum motor starting capabilities. The
excitation does not have a
“fixed ceiling”
and responds
according the demands of the required load.
ENGINE
The DCA45SSIU4 is powered by a 4 cylinder, water
cooled, direct injection, turbocharged ISUZU 4JJ1T diesel
engine. This engine is designed to meet every performance
requirement for the generator. Reference Table 2 for engine
specifications.
In keeping with MQ Power’s policy of constantly improving
its products, the specifications quoted herein are subject
to change without prior notice.
eleCtrIC governor SYStem
The electric governor system controls the RPMs of the engine.
When the engine demand increases or decreases, the
governor system regulates the frequency variation to ±.25%.
extenSIon CableS
When electric power is to be provided to various tools or
loads at some distance from the generator, extension cords
are normally used. Cables should be sized to allow for
distance in length and amperage so that the voltage drop
between the generator and point of use (load) is held to
a minimum. Use the cable selection chart (Table 6) as a
guide for selecting proper extension cable size.
generaL infOrMatiOn
Summary of Contents for Power WhisperWatt DCA45SSIU4
Page 19: ...DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 page 19 Notes...
Page 52: ...page 52 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 GENERATOR ASSY...
Page 54: ...page 54 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 56: ...page 56 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 58: ...page 58 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 66: ...page 66 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 BATTERY ASSY...
Page 68: ...page 68 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 Muffler Assy...
Page 70: ...page 70 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 FUEL TANK ASSY...
Page 76: ...page 76 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 RUBBER SEALS ASSY...
Page 81: ...DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 page 81 notes...