page 18 — DCa45SSIU4 60 hz generator • operatIon anD partS manUal — rev. #1 (10/24/13)
generatOr cOntrOL paneL
Figure 4. Generator Control Panel
1000
2000
3000
0
R P M
OFF
W
U
V
OFF
W-U
V-W
U-V
DECREASE
INCREASE
AUTO
MANUAL
OFF/RESET
LOW OIL PRESSURE
HIGH COOLANT TEMPERATURE
OVERCRANK
OVERSPEED
ENGINE RUNNING
MOOOOO-20001Q
1
2
4
3
6
7
5
The definitions below describe the controls and functions
of the DCA45SSIU4 Generator Control Panel (Figure 4).
1.
voltage regulator Control
— Allows ±15% manual
adjustment of the generator’s output voltage.
2.
main Circuit breaker
—This three-pole, 110A main
breaker is provided to protect the the U,V, and W
Output Terminal Lugs from overload.
3.
Ammeter Change-Over Switch
— This switch allows
the AC ammeter to indicate the current flowing to the
load connected to any phase of the output terminals,
or to be switched off. This switch does not effect the
generator output in any fashion, it is for current reading
only.
4.
voltmeter Change-over Switch
— This switch allows
the AC voltmeter to indicate phase to phase voltage
between any two phases of the output terminals or to
be switched off.
5.
aC voltmeter
— Indicates the output voltage present
at the U,V, and W Output Terminal Lugs.
6.
AC Ammeter
— Indicates the amount of current the
load is drawing from the generator per leg selected by
the ammeter phase-selector switch.
7.
Frequency meter
— Indicates the output frequency
in hertz (Hz). Normally 60 Hz.
Located behind the generator control panel is the Generator
Control Box. This box contains some of the necessary
electronic components required to make the generator
function.
The Control Box is equipped with the following major
components:
Over-Current Relay
Automatic Voltage Regulator (AVR)
Starter Relay
Current Transformer
Voltage Selector Switch
Main Circuit Breaker
NOTICE
Remember the
overcurrent relay
monitors the current
flowing from the
U,v, and W output terminal lugs
to the load.
In the event of a short circuit or over current condition,
it will automatically trip the 110 amp main breaker.
To restore power to the
Output Terminal Panel
, press
the reset button on the overcurrent relay and place the
main
circuit breaker in the
closed
position (
ON
).
Summary of Contents for Power WhisperWatt DCA45SSIU4
Page 19: ...DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 page 19 Notes...
Page 52: ...page 52 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 GENERATOR ASSY...
Page 54: ...page 54 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 56: ...page 56 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 58: ...page 58 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 66: ...page 66 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 BATTERY ASSY...
Page 68: ...page 68 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 Muffler Assy...
Page 70: ...page 70 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 FUEL TANK ASSY...
Page 76: ...page 76 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 RUBBER SEALS ASSY...
Page 81: ...DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 page 81 notes...