page 26 — DCa45SSIU4 60 hz generator • operatIon anD partS manUal — rev. #1 (10/24/13)
generatOr Outputs
generator oUtpUt voltageS
A wide range of voltages are available to supply voltage for
many different applications. Voltages are selected by using
the
voltage selector
switch
(Figure 13). To obtain some of
the voltages as listed in Table 7 (see below) will require a
fine adjustment using the
voltage regulator
(VR)
control
knob
located on the control panel.
voltage Selector Switch
The voltage selector switch (Figure 13) is located above
the output terminal panel’s Hard Wire Hook-up Panel. It
has been provided for ease of voltage selection.
Figure 13. Voltage Change-Over Board
voltage Selector Switch locking button
The voltage selector switch has a locking button to protect
the generator and load from being switched while the
engine is running. To lock the voltage selector switch, press
and hold the red button located at the bottom of the switch.
CAUTION
never
change the position of the
voltage selector
switch
while the engine is running.
alWaYS
place
circuit breaker in the
OFF
position before selecting
voltage
.
table 7. voltages available
Three Phase
(Switchable)
208V
220V
240V
416V
440V
480V
Single Phase
(Switchable)
120V
1127V
139V
240V
254V
277V
Generator Amperage
Table 8 shows the
maximum
amps the generator can
provide.
DO NOT
exceed the maximum amps as listed..
gFCI receptacle load Capability
The load capability of the GFCI receptacles is directly
related to the voltage being supplied at either the output
terminals or the 2 twist lock auxiliary receptacles.
Tables 9 and 10 show what amount of current is available
at the GFCI receptacles when the output terminals and
twist lock receptacles are in use. Be careful that your load
does not to exceed the available current capability at the
receptacles.
table 8. generator maximum amps
rated voltage
maximum amps
1Ø 120 Volt
100 amps (4 wire)
1Ø 240 Volt
50 amps (4 wire)
3Ø 240 Volt
108 amps
3Ø 480 Volt
54 amps
table 9. 1Ø gFCI receptacle load Capacity
KW in Use
twist lock (C6369)
available load
Current (amps)
1Ø 240/120V
GFCI Duplex
5-20R 120V
26.0
0
24.8
5 amps/receptacle
23.6
10 amps/receptacle
22.4
15 amps/receptacle
21.2
20 amps/receptacle
table 10. 3Ø gFCI receptacle load Capacity
Kva in Use
(UvWo terminals)
available load
Current (amps)
3Ø 240/480V
GFCI Duplex
5-20R 120V
45
0 amps/receptacle
40.9
5 amps/receptacle
36.7
10 amps/receptacle
32.6
15 amps/receptacle
28.4
20 amps/receptacle
Summary of Contents for Power WhisperWatt DCA45SSIU4
Page 19: ...DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 page 19 Notes...
Page 52: ...page 52 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 GENERATOR ASSY...
Page 54: ...page 54 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 56: ...page 56 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 58: ...page 58 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 control box ASSY...
Page 66: ...page 66 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 BATTERY ASSY...
Page 68: ...page 68 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 Muffler Assy...
Page 70: ...page 70 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 FUEL TANK ASSY...
Page 76: ...page 76 DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 RUBBER SEALS ASSY...
Page 81: ...DCA45SSIU4 60 hz Generator operation and parts manual rev 1 10 24 13 page 81 notes...