DCA-125USJ — OPERATION AND PARTS MANUAL — REV. #2 (01/27/11) — PAGE 39
1
DCA-125USJ — GENERATOR SHUT-DOWN PROCEDURE
Normal Shutdown Procedure
To shutdown the generator use the following procedure:
1. Place both the
MAIN
,
GFCI
and
LOAD
circuit breakers
as shown in Figure 38 to the
OFF
position.
3. Let the engine cool by running it at low speed for 3-5
minutes with no load applied.
4. Place the
MPEC Control Switch
(Figure 55) to the
OFF/RESET
position.
Figure 55. MPEC Control Switch (Off/Reset)
5. Verify that the
all
status LED’s on the MPEC display
are
OFF
(not lit).
6. Remove all loads from the generator.
7. Inspect entire generator for any damage or loosening of
components that may have occured during operation.
Emergency Shutdown Procedure
1. To shut-down the engine in the event of an emergency,
switch the
MAIN
,
GFCI
and
LOAD
(Figure 38) circuit
breakers to
OFF
position.
2. Place the
MPEC Control Switch
switch (Figure 55) to
the
OFF/RESET
position.
NEVER
stop the engine suddenly except in an emergency.
WARNING - SHUTTING DOWN THE GENERATOR