circuit Breakers
To protect the generator from an overload, a 3-pole, 400
amp, main circuit breaker is provided to protect the
u,v,
and W Output Terminals
from overload. In addition two
single-pole, 20 amp
gfci
circuit breakers are provided to
protect the GFCI receptacles from overload. Three 50 amp
load
circuit breakers have also been provided to protect
the auxiliary receptacles from overload. Make sure to itch
all
circuit breakers to the
OFF
position prior to starting
the engine.
luBrication oil
Fill the engine crankcase with lubricating oil through the
filler hole, but
DO NOT
overfill. Make sure the generator is
level and verify that the oil level is maintained between the
two notches (Figure 26) on the dipstick. See Table 9 for
proper selection of engine oil.
Figure 26. Engine Oil Dipstick
When checking the engine oil, be sure to check if the oil is
clean. If the oil is not clean, drain the oil by removing the
oil drain plug, and refill with the specified amount of oil as
outlined in the
john deere owner’s manual
. Oil should
be warm before draining.
Delo® engine oil is the recommended engine oil for this
generator. When replacing engine oil please refill using
Delo® 400 LE SAE 15W-40 (API CJ-4) engine oil.
table 9. recommended motor oil
fuel check
Refilling the Fuel System
This generator has an internal fuel tank located inside
the trailer frame and may also be equipped with an
environmental fuel tank (Figure 27).
alWaYs
fill the fuel
tanks with clean fresh
#2 diesel fuel. do not
fill the fuel
tanks beyond their capacities.
Pay attention to the fuel tank capacity when replenishing
fuel. The fuel tank cap must be closed tightly after filling.
Handle fuel in a safety container. If the container does not
have a spout, use a funnel. Wipe up any spilled fuel
immediately.
Figure 27. Internal Fuel Tank System
DANGER
Fuel spillage on a
hot
engine can cause
a
fire
or
explosion
. If fuel spillage occurs,
wipe up the spilled fuel completely to
prevent fire hazards.
never
smoke
around or near the generator.
caution
onlY properly trained personnel
who have read
and understand this section should refill the fuel tank
system.
Generator Internal Fuel Tank
Trailer Fuel Tank
150
Summary of Contents for Whisperwatt DCA150SSJU4F
Page 5: ...DCA150ssju4f 60 hz generator operation manual rev 0 11 0614 page 5 notes ...
Page 56: ...page 56 dca150ssju4f 60 hz generator operation and Parts manual rev 0 11 06 14 GENERATOR ASSY ...
Page 72: ...page 72 dca150ssju4f 60 hz generator operation and Parts manual rev 0 11 06 14 battery ASSY ...
Page 74: ...page 74 dca150ssju4f 60 hz generator operation and Parts manual rev 0 11 06 14 muffler ASSY ...
Page 78: ...page 78 dca150ssju4f 60 hz generator operation and Parts manual rev 0 11 06 14 fuel tank ASSY ...
Page 80: ...page 80 dca150ssju4f 60 hz generator operation and Parts manual rev 0 11 06 14 ENCLOSURE ASSY ...
Page 93: ...DCA150ssju4f 60 hz generator operation manual rev 0 11 0614 page 93 notes ...