- If R2M ( Relay-2 mode ) is selected as R1 ( Relay-1 ), all the setting done for
Relay-1 will be automatically set for Relay-2.
Specifications are subject to change, since development is a continuous process,
So for more updated operating information and Support,
Please contact our Helpline: 9978991474/76/82 or
Email at
Ver:191201
service@multispanindia.com
- If Reset Mode Selected As ZVR ( Zero Value Reset ), then the Relay will be reset
after Selected Reset time once the healthy condition achieved OR Zero Value
reached.
Press key for save & exit
SET
Password
p a s
3 7
P D L
(Power On Delay Time)
5
(0-99 Sec.)
T D L
R s t
(Trip Delay Time)
(Reset mode)
(Auto / Manual / ZVR Reset)
S
a u t
r C t
5
(0-999 Sec.)
(Recovery time)
R F M
p F M
(Relay Fault Mode)
(Power Fail Fault memory)
O N
y e s
(ON/OFF)
(Yes/No)
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
Press key
SET
SET
Press key
Press key
Press key
Press key
SET
SET
SET
SET
Press key
Press key
Press key
Press key
SET
SET
SET
SET
Enter Password 37
(0 to 99 sec.)
If Auto/ ZVR Reset mode select
n t w
(Network selection)
3 p 4
(
3Ø-3W/3Ø-4W/1Ø-2W )
Press key
SET
Press key
for 5 sec
SET
If Manual
Reset mode
select
4 0 0
Scroll
u v
3 2 0
Scroll
O F
5 2
.
0
Scroll
Over Frequency Fault
Over Frequency
Value=52.0 Hz
◘
◘
U F
A S
P L
P S
◘
◘
◘
◘
◘
◘
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
Note : LED Status- blinking LED LED on LED off
O V
4 9
.
5
2 0
Scroll
Scroll
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
Under Frequency Fault
Asymmentry Voltage
between y & B Phase
L1 - Phase loss
Phase sequence Fault
Under Frequency
Value=49.5 Hz
Asymmentry Percentage
= 20 %
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
L1 L2 L3
R1 R2
Over Voltage in
V (3Ø-3W) or V
Over Voltage Value=400V
◘
◘
L1L2
L1
(3Ø-4W)
Under Voltage in
V (3Ø-3W) or V
Under Voltage Value=320V
L2L3
L2
(3Ø-4W)
If Under Voltage is Enable
Password
p a s
9 7
(Relay - 2 Mode)
R 1
(Relay -1 / Relay -2)
O V 2
(Over Voltage Of Relay-2)
If
R 2
is Selected
2 8 0
(Over Voltage Value)
U V 2
(Under Voltage of Relay-2)
2 8 0
(Under Voltage Value)
O F 2
(Over Frequency of Relay-2)
4 5 0
(Over Frequency Value)
(45.0-60.0 Hz)
U F 2
(Under Frequency of Relay-2)
5 5
.
0
(Under Frequency Value)
(45.0-65.0 Hz)
A S 2
(Asymmetry Percentage
Of Relay -2)
2 O
(Asymmetry Percentage)
(2-30%)
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key
SET
Press key for save & exit
SET
If Under
Voltage
is Disable
Press key
for 5 sec
Enter Password 97
SET
Relay-2 Settings
Password 73
:
Relay 1 Settings
Password 97
:
Relay 2 Settings
( Relay -1 & Relay -2 Settings : To Set
Trip Value Of Over Voltage, Under
Voltage, Over Frequency, Under
Frequency, Asymmetry Percentage )
If Over
Voltage
is Disable
If over voltage is enable
If Over Frequency is Enable
If Under Frequency is Enable
If Over
Frequency
Is Disable
If Under
Frequency
is Disable
If Asymmetry is Enable
If
Asymmetry
is Disable
(
85-550V For 3Ø-3W )
(50-330V For 3Ø-4W/1Ø-2W
)
(
85-520V For 3Ø-3W )
(50-300V For 3Ø-4W/1Ø-2W
)
IF 3Ø-4W/3Ø-3W Selected
1Ø-2W
Selected
IF
SET
FAULT MESSAGE
Page -4
NOTE :-