background image

4

4.0 Flow Protection

Proof of chilled water and condenser water flow is required by the Master Control inputs.  Paddle-type or Differential Pressure (DP) switches may be used.  
Switches are a Multistack option, otherwise they are to field supplied and installed.  Chillers purchased with chilled or condenser water pump modules have a 
DP switch installed across the pump to verify it is running. Multistack recommends a paddle-type switch be installed in the leaving water piping of the chiller, 
or if using a differential pressure switch install it across the inlet and outlet water connections to the chilled and/or condenser water piping connections.

5.0 System Water Volume

Chilled water systems remove the thermal gain from the process of cooling. A properly sized chilled water system will have enough time to properly control, 
respond to changes in load, and prevent short cycling of the chiller. To ensure the system water volume is adequate, a general rule of thumb is: 

7-10 gallons of water per ton

or

Acceptable Chilled Water Volume = Chilled Water Design GPM X 3 

In the event the system components can’t hold the necessary chilled water volume, a properly sized chilled water storage tank should be added. 

6.0 Electrical Data

Field wiring should be done in accordance with all federal, state and local regulations. Breakers, fuses, wire, and wire size must be sized and installed per the 
National Electric Code (NEC). Applied voltage to all Multistack chillers must be ± 10% of the unit’s nameplate voltage. The voltage imbalance between phases 
must not exceed 2%. According to NEMA Standard MG-1-1998, a 2% voltage imbalance will cause a current imbalance of 6 to 10 times the voltage imbalance. 
It is very important to keep the unbalance between electrical phases to a minimum. 

There will always be one module in the bank that is the Master Module.  This module contains the Master Control Board (far left) as well as the module Slave 
Board (right of the master).  Condenser fan control will either be by on/off pressure control or VFDs.  Compressors use contactors as starters and circuit breakers 
for high and low voltage components.  The main power input block is located to the right of the circuit breakers.  A module Auto / Off / Manual Mode switch 
is also available for back up control if the master board would fail.  The master module also has the terminal strip inputs for flow switches, start/stop, alarm 
output, and phase monitor. When shipped the master control panel will also contain the P-Lan communication wire to be field installed and the system 
Leaving Chilled Water Sensor well to be field installed.

7.0 Identification and Explanation of Components

7.1 Master Module Control Panel

There will always be one module in the bank that is the Master Module.  This module contains the Master Control Board (far left) as well as the module Slave 
Board (right of the master).  Condenser fan control will either be by on/off pressure control or VFDs.  Compressors use contactors as starters and circuit breakers 
for high and low voltage components.  The main power input block is located to the right of the circuit breakers.  A module Auto / Off / Manual Mode switch 
is also available for back up control if the master board would fail.  The master module also has the terminal strip inputs for flow switches, start/stop, alarm 
output, and phase monitor. When shipped the master control panel will also contain the P-Lan communication wire to be field installed and the system 
Leaving Chilled Water Sensor well to be field installed.

Summary of Contents for Airstack ASPX Series

Page 1: ...ASP X Chiller Modules Operation and Maintenance Manual...

Page 2: ...or Oil Level 8 13 0 Refrigerant Charge Evacuation 8 14 0 Filter Driers 8 15 0 Condenser Fan Control 8 16 0 Superheat Subcooling 8 17 0 Pressure Relief Valve 9 18 0 Annual Maintenance 9 19 0 Compressor...

Page 3: ...hemoduleMasterControl When theEnteringChilledWatersensorsendsthesignaltotheMasterControlthatCoolingisneeded compressorswillbegintostartandproduceChilledWater The pointatwhichtheEnteringChilledWatertem...

Page 4: ...tageimbalance It is very important to keep the unbalance between electrical phases to a minimum There will always be one module in the bank that is the Master Module This module contains the Master Co...

Page 5: ...e Master Module has and Entering Chilled Water Sensor A System Leaving ChilledWater Sensor is shipped in the electrical panel of the Master Module and should be field installed 2 10 after the first mo...

Page 6: ...ver ChillerModulesuseamechanicalexpansionvalveforrefrigerantcontroltotheevaporator Superheatshouldbesettoapproximately10 12 F TheLiquidLine Solenoid is used to prevent refrigerant migration into the e...

Page 7: ...age of this manual is an information log sheet for the chiller The log sheet can be used daily weekly or as desired to record operation characteristics of the chiller The information recorded on the l...

Page 8: ...level should be maintained at 1 8 full To ensure no liquid is present in the oil the crankcase heaters should be on 24 hours before starting of the compressors Factory oil charge volume for each comp...

Page 9: ...L stainless steel and copper Do not use bleach or hydrochloric or sulfuric acids 18 4 Condenser Coils The condenser side coils should be cleaned periodically of air born debris to maximize efficiency...

Page 10: ...tothecompressoritisrecommendedthecompressorbereplacedasremovingallthemoisture from the oil is very difficult Replacement of the condenser side heat exchanger the expansion valve and installation of a...

Page 11: ...icalmodulethroughthebottomheadersothemechanicalmodulebottomheader will connect with the free cool module bottom header Leaving chilled water can the either exit the chiller through the free cool modul...

Page 12: ...ebottomofthetankandpouritbackintothetankinadifferentlocationmixing the solution PressureGauge Thepressuregaugeshowsthepressurethatthechilledwaterloopisoperatingat ItisalsoshowingwhatthePressureRegulat...

Page 13: ...mode On a normal application without water valves if you have 10 compressors and flow at a true 10 F DeltaT with setpoints of 55 Up and 45 Lo andVSP at 50 your no load point would be 50 F The last mo...

Page 14: ...setpoints in system variables Check for flow restriction No Demand Check entering ECHW sensor Check setpoints in system variables Check sensor location 100 Demand all the time Check entering CHW senso...

Page 15: ...Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 Ent Chw Lvg Chw Demand Capacity System Upset Loset VSP Load Limit Tdiff Index Sy...

Page 16: ...F162ASP O M 072610 1064 Maple Avenue Sparta WI P 608 366 2400 F 608 366 2450 www multistack com...

Reviews: