background image

11.0 Strainer Cleaning

All ASPX modules have a 30-mesh filter strainer in the Chilled Water inlet header.  The purpose for the filter strainer is to keep debris from entering the heat 
exchanger.  An external “Y” or basket type system strainer should also be installed as a pre-filter to the factory supplied strainers.

There is no set time for cleaning the filter strainers.  The frequency of this process is dependant on the water quality in the Chilled Water loop.  Normally, debris 
in a water loop is going to take the path of least resistance and build up on the last modules to receive water.  

If circuits are faulting on Low Suction Temperature, or Low Chilled Water Temperature the Chilled Water inlet filter cartridge should be checked.  The strainers 
are located in the top header on the Chilled Water side.  If the strainers are clean, the fault is most likely being caused by a low flow condition--or set-points 
in the master control that are too low.  If these possibilities are eliminated, the Chilled Water heat exchangers may need cleaning.

Steps to remove the strainers for cleaning

1. Stop Chilled water pump and shut down chiller.
2. Close inlet and outlet water valves to the chilled water
3. Drain the water/glycol from the top header in the end module so the strainers can be removed.
4. Remove the 4-8” Victaulic end cap on last module.
5. Remove strainers and clean.  You may need to make a tool to hook the other strainers for removal.
6. Re-install clean strainers.
7. Open the bottom water isolation valve and fill unit from the bottom up to prevent air from being trapped.
8. Restart Chilled Water pump, bleed any air and start Chiller.

12.0 Compressor Oil Level

Compressors used on ASPX modules are oil charged by the compressor manufacturer.  The standard tandem Copeland compressors do have an oil equalizer 
line and oil level sight glass indicator.  Oil level should be maintained at 1⁄8 – ¼ full.

To ensure no liquid is present in the oil the crankcase heaters should be on 24 hours before starting of the compressors.

Factory oil charge volume for each compressor can be found in section 13.0.

13.0 Refrigerant Charge/Evacuation

All ASPX modules are factory charged with the recommended refrigerant volume.  Prior to charging, each circuit is evacuated to a maximum of 150 microns 
and held 15 minutes.  The proper refrigerant charge for each module can be found on the module data plate.  

On air-cooled packaged machines, the proper charging procedure is calculated by the weigh-in method.  Charging to a full sight glass on air-cooled ma-
chines will likely result in over charging because the elbows in the liquid line, as well as the liquid line solenoid valve, still produce some flashing--even with 
the correct charge.  As fans are cycling, the sight glass will also display some bubbling.

 

Model # 

Lbs. R410a  Lbs. Low Ambient 

Total Tandem Compressor Oil Charge

 ASP10X 

50 

90 

114 

oz.

 ASP15X 

60 

85 

220 

oz.

 ASP20X 

100 

100 

220 

oz.

 ASP30X 

125 

125 

252 

oz.

 ASP60X 

220 

360 

426 

oz.

14.0 Filter Driers

ASPX Chiller modules have a liquid line filter drier installed.    When doing a repair to the refrigerant side because of a compressor motor burn, or moisture 
entering the system, a proper replacement drier should be installed.

15.0 Condenser Fan Control

10-, 15- and 20-ton modules can be ordered with standard pressure control cycling of fans or optional VFD control.  ASP30 and ASP60 modules come standard 
with VFD control.

16.0 Superheat/Subcooling

ASPX modules use a mechanical expansion valve.  By turning the valve adjustment clockwise superheat is increased.

On each module, superheat is set at the factory during the run test.  Superheat is set between 10 – 12°F during the test run. 

Subcooling is necessary in the system to prevent flash gas when the refrigerant enters the expansion valve.  ASPX condensers are sized so that subcooling of 
the liquid refrigerant will take place without a separate subcooler.  The general range of subcooling seen is 7- 15°F.  

Summary of Contents for Airstack ASPX Series

Page 1: ...ASP X Chiller Modules Operation and Maintenance Manual...

Page 2: ...or Oil Level 8 13 0 Refrigerant Charge Evacuation 8 14 0 Filter Driers 8 15 0 Condenser Fan Control 8 16 0 Superheat Subcooling 8 17 0 Pressure Relief Valve 9 18 0 Annual Maintenance 9 19 0 Compressor...

Page 3: ...hemoduleMasterControl When theEnteringChilledWatersensorsendsthesignaltotheMasterControlthatCoolingisneeded compressorswillbegintostartandproduceChilledWater The pointatwhichtheEnteringChilledWatertem...

Page 4: ...tageimbalance It is very important to keep the unbalance between electrical phases to a minimum There will always be one module in the bank that is the Master Module This module contains the Master Co...

Page 5: ...e Master Module has and Entering Chilled Water Sensor A System Leaving ChilledWater Sensor is shipped in the electrical panel of the Master Module and should be field installed 2 10 after the first mo...

Page 6: ...ver ChillerModulesuseamechanicalexpansionvalveforrefrigerantcontroltotheevaporator Superheatshouldbesettoapproximately10 12 F TheLiquidLine Solenoid is used to prevent refrigerant migration into the e...

Page 7: ...age of this manual is an information log sheet for the chiller The log sheet can be used daily weekly or as desired to record operation characteristics of the chiller The information recorded on the l...

Page 8: ...level should be maintained at 1 8 full To ensure no liquid is present in the oil the crankcase heaters should be on 24 hours before starting of the compressors Factory oil charge volume for each comp...

Page 9: ...L stainless steel and copper Do not use bleach or hydrochloric or sulfuric acids 18 4 Condenser Coils The condenser side coils should be cleaned periodically of air born debris to maximize efficiency...

Page 10: ...tothecompressoritisrecommendedthecompressorbereplacedasremovingallthemoisture from the oil is very difficult Replacement of the condenser side heat exchanger the expansion valve and installation of a...

Page 11: ...icalmodulethroughthebottomheadersothemechanicalmodulebottomheader will connect with the free cool module bottom header Leaving chilled water can the either exit the chiller through the free cool modul...

Page 12: ...ebottomofthetankandpouritbackintothetankinadifferentlocationmixing the solution PressureGauge Thepressuregaugeshowsthepressurethatthechilledwaterloopisoperatingat ItisalsoshowingwhatthePressureRegulat...

Page 13: ...mode On a normal application without water valves if you have 10 compressors and flow at a true 10 F DeltaT with setpoints of 55 Up and 45 Lo andVSP at 50 your no load point would be 50 F The last mo...

Page 14: ...setpoints in system variables Check for flow restriction No Demand Check entering ECHW sensor Check setpoints in system variables Check sensor location 100 Demand all the time Check entering CHW senso...

Page 15: ...Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 Ent Chw Lvg Chw Demand Capacity System Upset Loset VSP Load Limit Tdiff Index Sy...

Page 16: ...F162ASP O M 072610 1064 Maple Avenue Sparta WI P 608 366 2400 F 608 366 2450 www multistack com...

Reviews: