background image

9

17.0 Pressure Relief Valve

Each module has a 650 psig pressure relief valve.  The relief valve is installed on the receiver of the module and has a 3/8” thread connection.

18.0  Annual Maintenance

18.1 Electrical Components

a.  Check all external interlocks.
b.  Inspect compressor terminals.
c.  Check compressor crankcase heater operation.
d. Tighten all contactors, relay and circuit breaker terminals.
e.  Check and calibrate all compressor safety controls.
f.  Check and record voltages and amperages for compressors.
g.  Check and record amperages for pumps and condenser fans.
h. Check and calibrate low ambient/ fan cycling controls.
i.  Inspect relay contacts for damage or pitting.

18.2 Refrigeration Circuits

a.  Analyze refrigerant with tube type moisture/acid analyzer.
b.  Check and record refrigerant subcooling and superheat.
c.  Check liquid solenoid valves.
d. Check expansion valve and sensing bulb connections.

18.3 Chilled Water System

a.  Clean pump strainers and system strainers.
b.  Remove header caps and clean the ECHW strainers.
c.  Check glycol, inhibitor content in system chilled water.
d.  In severe cases where the chilled side water is contaminated the heat exchangers may need to be backflushed.  Multistack has available a cleaning kit 

do to this task.  Please contact Multistack for more information if heat exchanger cleaning is needed.  Be sure to use only chemicals compatible with 
316L stainless steel and copper.  Do not use bleach, or hydrochloric or sulfuric acids.

18.4 Condenser Coils.

The condenser side coils should be cleaned periodically of air born debris to maximize efficiency and heat exchange.  Coil cleaner compatible with aluminum 
and copper can be used.  Coils can be washed with a garden hose or if careful a pressure washer.  Be sure to wash the debris out from the backside of the coils 
in order to avoid further compacting debris into the coils.

18.5 Cabinet and Related Hardware

a.  Dry clean electrical panels, remove debris.
b.  Apply protective coatings or wax if required.

19.0 Compressors

With any chiller system there is always the chance of compressor failure.  In the event of a failure, proper steps should be taken to determine the cause of the 
failure.  

1. A motor burn due to a fault in the motor insulation is quite rare.  Most burnouts are actually caused by a mechanical condition or lubrication problems.  

In the event of a burnout, proper clean up procedures should be followed.  

2. Check all electrical components of the circuit (contactors, fuses, wires,  etc.).
3. If necessary, do a system clean up.  Nu-Calgon RX-11 Flush, or Sporlan System Cleaner work well.
4. Replace the liquid line filter drier with burnout core.
5. Evacuate the system to a minimum of 500 microns and hold for 20 minutes.
6. Charge the circuit with virgin refrigerant.  Charge with liquid into the discharge side.  See refrigerant charge on nameplate data of unit.
7. Run the system with a burnout filter core for two-to-three weeks, then replace it with a standard core drier.

Summary of Contents for Airstack ASPX Series

Page 1: ...ASP X Chiller Modules Operation and Maintenance Manual...

Page 2: ...or Oil Level 8 13 0 Refrigerant Charge Evacuation 8 14 0 Filter Driers 8 15 0 Condenser Fan Control 8 16 0 Superheat Subcooling 8 17 0 Pressure Relief Valve 9 18 0 Annual Maintenance 9 19 0 Compressor...

Page 3: ...hemoduleMasterControl When theEnteringChilledWatersensorsendsthesignaltotheMasterControlthatCoolingisneeded compressorswillbegintostartandproduceChilledWater The pointatwhichtheEnteringChilledWatertem...

Page 4: ...tageimbalance It is very important to keep the unbalance between electrical phases to a minimum There will always be one module in the bank that is the Master Module This module contains the Master Co...

Page 5: ...e Master Module has and Entering Chilled Water Sensor A System Leaving ChilledWater Sensor is shipped in the electrical panel of the Master Module and should be field installed 2 10 after the first mo...

Page 6: ...ver ChillerModulesuseamechanicalexpansionvalveforrefrigerantcontroltotheevaporator Superheatshouldbesettoapproximately10 12 F TheLiquidLine Solenoid is used to prevent refrigerant migration into the e...

Page 7: ...age of this manual is an information log sheet for the chiller The log sheet can be used daily weekly or as desired to record operation characteristics of the chiller The information recorded on the l...

Page 8: ...level should be maintained at 1 8 full To ensure no liquid is present in the oil the crankcase heaters should be on 24 hours before starting of the compressors Factory oil charge volume for each comp...

Page 9: ...L stainless steel and copper Do not use bleach or hydrochloric or sulfuric acids 18 4 Condenser Coils The condenser side coils should be cleaned periodically of air born debris to maximize efficiency...

Page 10: ...tothecompressoritisrecommendedthecompressorbereplacedasremovingallthemoisture from the oil is very difficult Replacement of the condenser side heat exchanger the expansion valve and installation of a...

Page 11: ...icalmodulethroughthebottomheadersothemechanicalmodulebottomheader will connect with the free cool module bottom header Leaving chilled water can the either exit the chiller through the free cool modul...

Page 12: ...ebottomofthetankandpouritbackintothetankinadifferentlocationmixing the solution PressureGauge Thepressuregaugeshowsthepressurethatthechilledwaterloopisoperatingat ItisalsoshowingwhatthePressureRegulat...

Page 13: ...mode On a normal application without water valves if you have 10 compressors and flow at a true 10 F DeltaT with setpoints of 55 Up and 45 Lo andVSP at 50 your no load point would be 50 F The last mo...

Page 14: ...setpoints in system variables Check for flow restriction No Demand Check entering ECHW sensor Check setpoints in system variables Check sensor location 100 Demand all the time Check entering CHW senso...

Page 15: ...Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 Ent Chw Lvg Chw Demand Capacity System Upset Loset VSP Load Limit Tdiff Index Sy...

Page 16: ...F162ASP O M 072610 1064 Maple Avenue Sparta WI P 608 366 2400 F 608 366 2450 www multistack com...

Reviews: