ACTION : Click on >>
Button.
COMMENTS :
Output 3 = Hz. (This
appears in Node No 1 Box)
3.6 Selecting Output Values & Ranges For Analogue
Outputs.
The mA output range is specified at 20mA = 100%. All
following mA values are available 0-1mA 0-5mA 0-10mA
and 4-20mA (any value between 1 & 20mA can be
specified) These values are entered as a percentage of
20mA.
Example :
Output 1 (I sum) = 4-20mA.
Output 2 (W3) = +10m-0-10mA- (Note all parameters that
can be read as bipolar (like Watts) the Multd2a program
automatically sets the outputs as bipolar outputs)
Output 3 (Hz) = 0-1mA.
ACTION : Click On Zero
Offset Box CH1.
COMMENTS :
Nominal Box is set at 100%
= 20mA . Zero offset box is
set at 0 = 0mA.
31
M560AT~1.PM5
01/08/101, 12:52
31