background image

LEGAL202107V01 

                                                                                      

 

 

3. 

Mechanical installation 

3.1. 

Selecting the location 

 

Select a suitable location for installing the modules. 

The modules should face south in northern latitudes and north in southern latitudes. 

For detailed information on the best installation angle, refer to standard solar photovoltaic installation 
guides or consult a reputable solar installer or systems integrator. 

Modules should not be shaded at any time. If a module is shaded or even partially shaded, it will fail to 
perform at ideal conditions and result in lower power output. A permanent and/or regular shade on the 
module voids the warranty. 

This installation manual is applicable for all PV system of 500 m or more away from the coastline. 

Do not use modules near equipment or in locations where flammable gases may be generated or collected. 

 

3.2. 

General Installation 

 

Before installing modules check for any optical deviations. Any optical deviations noticed after system 
installed may void warranty.  Any potential costs for labor, material or other cost such as documentation, 
safety or performing the (de/ re-) installation will not be covered.

 

The module mounting structure must be made of durable, corrosion-resistant and UV-resistant material. 
Always use a tested and certified mounting structure approved for your system design.

 

In regions with heavy snowfall in winter, select the height of the mounting system so that the lowest edge of 
the module is not covered by snow for any length of time. In addition, ensure that the lowest portion of the 
module is placed high enough so that it is not shaded by plants, trees or damaged by ground soil moved by 
or through the air. 

For ground mounting systems, the minimum distance we recommend from the ground to the bottom of the 
module is at least 24 inches (60cm). 

Modules must be securely attached to the mounting structure. For Clamping System installation methods, 
the recommended maximum compression for each clamp is 2900 PSI (20 MPA) in order to avoid potential 
damages to module frames. Follow the instruction of the clamping system supplier. 

Provide adequate ventilation under the modules in conformity to your local regulations. A minimum 
distance of 10 cm between the roof plane and the frame of the module is generally recommended. 

Always observe the instructions and safety precautions included with the module support frames. 

Before installing modules on a roof, always ensure the roof construction is suitable. In addition, any roof 
penetration required to mount the module must be properly sealed to prevent leaks. 

Dust building up on the surface of the module can impair with the module performance. The modules shall 

Summary of Contents for MSMD M10-60 Series

Page 1: ...M nchen Solar Installation Manual M nchen Energieprodukte GmbH www muenchen energieprodukte de...

Page 2: ...y 3 1 4 Fire Safety 4 2 Product Identification 5 3 Mechanical installation 6 3 1 Selecting the location 6 3 2 General Installation 6 3 3 Installation methods 7 3 4 Attachment guidelines 8 4 Electrical...

Page 3: ...t light energy to direct current electrical energy They are designed for outdoor use Modules can be ground mounted mounted on rooftops The proper design of support structures lies within the responsib...

Page 4: ...eriod of time always cover the modules and ensure that the glass faces down on a soft flat surface to prevent water from collecting inside the module and causing damage to exposed connectors 1 3 Insta...

Page 5: ...ctors to connect modules to form a string or connect to another device Removing the connectors will void the warranty 1 4 Fire Safety Consult your local authority for guidelines and requirements for b...

Page 6: ...o 1000 1500 volts while other UL products are 600 volts Check your nameplate or contact your local representative for details 2 Barcode each individual module has a unique serial number The serial num...

Page 7: ...ys use a tested and certified mounting structure approved for your system design In regions with heavy snowfall in winter select the height of the mounting system so that the lowest edge of the module...

Page 8: ...maximum permissible loads and are not subject to excessive forces due to the thermal expansion of thesupport structures Never allow modules overlap or exceeds the rooftop Refertothefollowinginstallati...

Page 9: ...t of 1600 Pa 0 232psi 2500 Pa 0 363 psi and 3600 Pa 0 522 psi respectively under UL 1703 standard The diagrams in the tables below are designed for illustration purpose For each installation modules c...

Page 10: ...0 Pa safety factor 1 5 M2 30 series M3 30 series M3 60 series M6 60 series Test load positive 5400 Pa negative 2400 Pa Design load positive 3600 Pa negative 1600 Pa safety factor 1 5 M2 30 series M3 3...

Page 11: ...Pa negative 3800 Pa Design load positive 3600 Pa negative 2533Pa safety factor 1 5 M2 30 series M3 30 series M3 60 series M6 60 series M6 72 series M10 60 series M10 72 series Clamp zone A 1 4 long f...

Page 12: ...sitive 5400 Pa negative 3800 Pa Design load positive 3600 Pa negative 2533Pa safety factor 1 5 M6 60 series M6 72 series M10 60 series M10 72 series Clamp zone A0 1 4 short frame length 50 mm A1 100 m...

Page 13: ...gative 3800 Pa Design load positive 3600 Pa negative 2533Pa safety factor 1 5 M2 30 series M3 30 series M3 60 series M6 60 series M6 72 series M10 60 series M10 72 series Attentions The module clamps...

Page 14: ...7V01 13 The mounting holes reserved for tracker mounting system with special accessories The length of module is over 2 meters whose load value with tracker needsto be confirmed by module supplier res...

Page 15: ...connected to the PV output Voltages are additive when modules are connected in series and modules currents are additive when Modules are connected in parallel as illustrated in Figure 1 Modules with...

Page 16: ...e maximum number of modules that can be connected in series within a string for the specific project must be calculated based on the actual local temperature If there is reverse current exceeding the...

Page 17: ...maximum series fuse rating of module and local electrical installation code always make sure M nchen Solar PV modules are assembled with the appropriate string fuse for circuit protection There is no...

Page 18: ...allation is finished and after connection to the grid please do a professional hand over to the owner including an installation protocol is required Provide a clear documentation of the system to the...

Page 19: ...F to bond solar modules to module mounting brackets grounding part is tested to UL467 3 Use WEEB DPF to bond solar modules to module mounting brackets grounding part is tested to UL467 Recommend faste...

Page 20: ...tions every six months to verify that they are clean secure undamaged and free of corrosion Or else the warranty may be voided In the event of a ground fault condition NEVER wash or spray modules with...

Reviews: