Ducted Split Type Air-Conditioning
38
13 Appendix
Air conditioner nominal working condition and working range:
Test condition
Indoor side
Outdoor side
DB( )
WB( )
DB( )
WB( )
Nominal cooling
27
19
35
24
Nominal heating
20
--
7
6
Rated cooling
32
23
43
26
Min. temp. for cooling
21
15
18(-15)
--
Rated heating
27
--
24
18
Min. temp. for heating
20
--
-7
-8
Note:
1. The design of this unit conforms to the requirements of EN14511 standard.
2. The air volume is measured at the relevant standard external static pressure.
3. Cooling (heating) capacity stated above is measured under nominal working conditions corresponding to
standard external static pressure. The parameters are subject to change with the improvement of products, in
which case the values on nameplate shall prevail.
4. In this table, the outdoor side 18(-15) DB (
) temperature of low-ambient cooling include two values, the
one in the bracket is the working condition of the appliance with function of low-ambient cooling . 18 is the
working condition for the unit without low ambient cooling fuction. -15 is the working condition for the unit
with low ambient cooling function.
WARNING!
This appliance is not intended for use by persons (including children) with reduced physical sensory or
capabilities, or leak of experience and knowledge, unless they have been given supervision on instruction
concerning use of appliance by a person responsible for their safety.
Children should be supervised to ensure that they do not play with the appliance.