ML180-MLT350 Dehumidifiers
14
2 Installation
190TGB-1034-A
2.11 Electrical Connections
2.11.1 Mains Supply
WARNING!
All electrical equipment connections must be carried out in
accordance with local regulations and by qualified personnel.
WARNING!
The unit must never be connected to a voltage or frequency other
than that for which it was designed and manufactured. Refer to the unit
identification plate if in doubt.
ML180 & MLT350 dehumidifiers are supplied complete with a pre-
wired mains cable. The cable is fitted with a multi-pin plug suitable for
connection to a single phase earthed mains socket.
The ML270 is designed for 3-phase AC operation. Each unit is supplied
complete with all the internal wiring installed and configured in
accordance with the specified voltage and frequency on the
identification plate.
ML270
(only): We strongly recommend that an external isolator be
installed and placed close to the ML270 unit. The isolator can be used
to switch of the power to the unit in case of an emergency.
NOTE!
Supply voltage must not vary more than 10% of the specified operating voltage.
The unit must be adequately connected to earth.
ML270
(only): The power supply cables must be of the correct size for
the dehumidifier being installed.
For connection details refer to the
identification plate
and
Electrical
Circuit Supplement
or refer to
section 6.5, Technical Specifications
.
2.12 External Humidistat
ML-Series dehumidifiers are pre-wired so that when the unit is in the
AUTomatic mode it can be controlled by an externally mounted
humidistat.
ML180-MLT350 have been designed with a one-step heater, and
therefore control is limited to switching the unit on and off using a one-
step humidistat.
A low voltage connector (mounted on the side of the unit) is provided
for electrical connection of a single-stage humidistat. For details refer
to the units
Circuit Diagram Supplement
.
2.12.1 Location Requirements
The humidistat should be mounted 1-1.5m above the floor and
positioned so that it is not exposed directly to dry air from the unit or
incoming moist air from opening and closing doors. It may not be
placed close to a heat source or so that it is exposed to direct sunlight.
2.12.2 Electrical Specifications
The humidistat connecting cable should have a conductor cross-
sectional area of not less than 0,75 mm
2
and must have an insulation
resistance rating in excess of 500 VAC.