ML180-MLT350 Dehumidifiers
18
3 Operation
190TGB-1034-A
3 Operation
3.1 General
The ML180-MLT350 dehumidifiers are equipped with a control panel
that contains mode switches and LED indicators.
The mode switch of the control panel has two operating modes:
MAN
(Manual mode)
The dehumidifiers fan, rotor and reactivation heater operate
continuously with full capacity.
AUT
(Automatic mode)
The dehumidifiers fan, rotor and reactivation heater operate when the
Relative Humidity rises above the desired value.
3.2 Safety
CAUTION!
To prevent damage to the fans, the unit must not be run for longer
than a few minutes prior to setting-up the process and reactivation airflows.
CAUTION!
Failure to correctly adjust the process and reactivations airflows
could cause the unit to malfunction.
3.3 Emergency stop
ML180 & MLT350
To start and stop the unit in normal operation the Run/Stop switch is
used. In case of an emergency unplug the unit from the wall outlet.
ML270
To start and stop the unit in normal operation the Run/Stop switch is
used. In case of an emergency switch the unit off using the external
isolator (if fitted).
3.4 Pre-Start Checks
Before starting the dehumidifier for the first time, carry out checks
according to
section 2.14, Pre-Start Checks
and
3.5 Operating the unit
3.5.1 Manual Mode
1. Ensure the Run/Stop switch is set to the
position.
2. Operate the mode switch to the
MAN
position.
3. Connect mains power to the unit and ensure that the power
connected indicator is illuminated.
4. Operate the run/stop switch to the
position. Ensure that the
unit running indicator is lit and the unit is operating.