ML180-MLT350 Dehumidifiers
190TGB-1034-A
2 Installation
15
The humidistat must be electrically compatible with the
dehumidifier’s extra low voltage control circuit.
The humidistat must be designed so that the contacts close on a
rising RH to complete the control circuit and start the dehumidifier.
Voltage drops may be experienced when using excessively long
cables.
At operation, the voltage must be 24VAC measured at the dedicated
terminals, used for connecting the humidistat to the dehumidifier. If
the measured voltage is less than 20VAC, a separate relay controlled by
the humdistat must be used.
2.13 Pre-Start settings
ML180-MLT350 units are equipped with a number of standard features
requiring a few selections and settings before the unit is put in
operation for the first time.
Some features require connection of external equipment. For wiring
details refer to the
Circuit Diagram Supplement
supplied with this unit.
2.13.1 One-step humidistat
NOTE!
Where no humidistat is connected to the unit, the dehumidifier will be operating
at maximum output for as long as the unit is switched on.
Where a one-step humidistat is fitted, the dehumidifier will switch on
and off under the control of the humidistat. The one-step humidistat is
connected in accordance with the
Circuit Diagram Supplement
.
2.14 Pre-Start Checks
Before starting the dehumidifier for the first time, ensure that the
mains power supply is isolated from the dehumidifier and carry-out the
following checks:
1. Check that the Mode switch on the dehumidifier is in the “OFF”
position,
.
2. Check the air intake filters for damage and proper fixation and also
check that all areas inside the unit are clean.
3. Visually inspect all ducting and duct connections to make sure that
all connections have been correctly installed and that there are no
signs of damage to the system. Also check that all ducts are free from
obstacles blocking the air passage.
4. Remove the top panel and check that none of the main contact
breakers in the electrical control panel have been tripped. For
details refer to the wiring diagrams provided with the unit.
5. Check that the incoming power supply voltage is correct and that
the cables are correctly connected.
6. If a humidistat has been installed, check that it has been correctly
positioned in the room and has been correctly connected to the
unit
see section 2.12, External Humidistat
.