MGS Installation and Operation Manual
26
1000-0085 Rev 0
Figure 9. Gas Cylinder and Test Hardware
Gas ampoules are convenient and inexpensive alternatives to using gas
cylinders for bump testing.
Step
Bump Testing Using Gas Ampoules
1
Make sure that both the ampoules and the calibration beaker are
clean and dry.
2
Unscrew the beaker hold screw and place the ampoule so that it
sits in the base of the beaker (see Figure 10).
3
Tighten the wing-nut screw onto
the ampoule without breaking it.
4
Remove the enclosure lid of the
gas detector.
5
Connect a voltmeter between pins
0V and VS to monitor sensor
response (in Volts DC).