6.6. Calibrating Electrochemical (EC) Sensors
There are two adjustments required: zero and span. They are monitored at 0V
and VS using a 0-5V scale. If the sensor range is 0-1000 ppm, then 5V=1000
ppm.
Step
Calibrating Electrochemical (EC) Sensors
1
Locate Pot VR201 which is used to adjust the zero point.
2
Monitor the output between 0V (negative) and VS (positive).
3
Adjust Pot VR201 to 0V or slightly positive (0.01 V is acceptable).
4
Locate Pot VR202 which is used to calibrate the range (span) of
the sensor.
5
Monitor the output between 0V (negative) and VS (positive).
6
Expose the sensor to calibration gas and allow to stabilise
(approximately 6 minutes).
7
Adjust pot VR202 to the voltage calculated in section 6.4 (page
28).
6.7. Calibrating Infrared (IR) Sensors
Step
Calibrating Infrared (IR) Sensors
1
Locate Pot VR203 which is used to adjust the zero point.
2
Monitor the output between 0V (negative) and VS (positive).
3
Expose the sensor to pure 99% nitrogen until output is stable
(approximately 3 minutes).
4
Adjust Pot VR203 to 0 V or slightly positive (0.01 V is acceptable).
5
Locate Pot VR202 which is used to calibrate the range (span) of
the sensor.
6
Monitor the output between 0V (negative) and VS (positive).
7
Expose the sensor to calibration gas and allow to stabilise
(approximately 3 minutes).
8
Adjust pot VR202 to the voltage calculated in section 6.4 (page
28).