3. Spa Assembly
1) Take the Thermal Ground Sheet and
position it where the footprint of the
spa will be. Take the body’s Vinyl Liner
and position it on top of the ground sheet.
2. Test RCD & Inflate Lid
a) Perform RCD Test
WARNING: RISK OF ELECTRIC SHOCK. The RCD plug must be
tested before each use. Do not use if RCD test fails.
1. Insert the plug into the power outlet.
2. Press the “RESET“ button, the indicator light will illuminate.
3. Press the “TEST” button, the indicator light turns off.
4. Press the “RESET” button, the indicator light will illuminate; the pump is ready to use
.
(1)
(2)
(3)
(4)
(8)
3) Assemble the remaining blank
Foam Panels until spa is
complete. As you assemble
the walls install the top and
bottom wall connectors
between the foam walls as
shown.
TIP:
Gripping the Foam Panel
on both sides and giving it a
small wiggle can help guide it
in if it gets stuck.
Ensure to insert the top and bottom
wall connectors as you assemble the
foam wall
2) Position Foam Panel 1 (with
holes - see fig.a), aligning it
exactly with the
corresponding holes in the
Vinyl Liner.
(fig.a)
b) Inflate the Lid
Connect the Inflation Hose to the Inflation Port on the PCU and then connect the other end
to the Inflation Port on the lid and press ‘JETS’ to inflate the lid. Once inflated close the Valve
Cap and press the ‘TEST’ button on the RCD to turn PCU off. When inflating, only top cap
on the Check Valve needs to be opened, when deflating lid, the entire valve should be un-
screwed.
NOTE:
Please disconnect the power after you inflate the top lip. The heater will
automatically turn on after 20 minutes of the Spa being plugged in. If there’s no water in the
Spa ,”E6” will appear after a few minutes and you will hear the noise of the filter pump dry
run. In this case, please switch off the power then ”E6” will automatically clear.