Torque Value
Model
Gauge
4KW
5KW
10 AWG
8 AWG
1.4~ 1.6Nm
1.4~ 1.6Nm
Ground (yellow-green)
L
LINE (brown or black)
N
Neutral (blue)
7
3KW
12 AWG
1.2~ 1.6Nm
AC Input/Output Connection
CAUTION!!
Before connecting to AC input power source, please install a separate AC breaker between inverter and
AC input power source. This will ensure the inverter can be securely disconnected during maintenance and fully
protected from over current of AC input. The recommended spec of AC breaker is32A for 3KW,40A for 4KW and 50A
for 5KW.
CAUTION!!
There are two terminal blocks with "IN" and "OUT" markings. Please do NOT-misconnect input and
output connectors.
WARNING!
All wiring must be performed by a qualified personnel.
WARNING!
It's very important for system safety and efficient operation to use appropriate cable for AC input
connection. To reduce risk of injury, please use the proper recommended cable size as below.
Suggested cable requirement for AC wires
Please follow below steps to implement AC input/output connection:
1. Before making AC input/output connection, be sure to open DC protector or disconnector first.
2. Remove insulation sleeve 10mm for six conductors. And shorten phase L and neutral conductor N 3mm.
3. Insert AC input wires according to polarities indicated on terminal block and tighten the terminal screws. Be sure
to connect PE protective conductor ( ) first.
Ground (yellow-green)
L
LINE (brown or black)
N
Neutral (blue)
WARNING:
Be sure to that AC power source is disconnected before attempting to hardwire it to the unit.
4. Then, insert AC output wires according to polarities indicated on terminal block and tighten terminal screws.
Be sure to connect PE protective conductor ( )first.
61
62
63
64
Warning Indicator
Warning Code
Warning Event
Icon flashing
Fan is locked when inverter is on.
Fan 2 is locked when inverter is on.
Battery is over-charged.
Low battery
22
67
70
72
73
74
75
76
77
Overload
Output power derating
Solar charger stops due to low battery
Solar charger stops due to high PV voltage
Solar charger stops due to over load
Solar charger over temperature
PV charger communication error
Parameter error
57
Inverter control current sensor error
58
Inverter output voltage is too low