Installation Manual
Type
:
HDR DIN rail power supply
(
Series
:
HDR-15, HDR-30, HDR-60, HDR-100
)
HDR-15-5
INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 5V 2.4A
HDR-15-12
INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 12V 1.25A
HDR-15-15
INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 15V 1.0A
HDR-15-24
INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 24V 0.63A
HDR-15-48
INPUT: 100-240VAC 0.5A 50/60Hz OUTPUT: 48V 0.32A
HDR-30-5
INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 5V 3.0A
HDR-30-12
INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 12V 2.0A
HDR-30-15
INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 15V 2.0A
HDR-30-24
INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 24V 1.5A
HDR-30-48
INPUT: 100-240VAC 0.88A 50/60Hz OUTPUT: 48V 0.75A
HDR-60-5
INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 5V 6.5A
HDR-60-12
INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 12V 4.5A
HDR-60-15
INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 15V 4.0A
HDR-60-24
INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 24V 2.5A
HDR-60-48
INPUT: 100-240VAC 1.8A 50/60Hz OUTPUT: 48V 1.25A
HDR-100-12
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 12V 7.1A
HDR-100-15
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 15V 6.13A
HDR-100-24
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 24V 3.83A
HDR-100-48
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 48V 1.92A
HDR-100-12N
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 12V 7.5A
HDR-100-15N
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 15V 6.5A
HDR-100-24N
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 24V 4.2A
HDR-100-48N
INPUT: 100-240VAC 3.0A 50/60Hz OUTPUT: 48V 2.1A
Introduction
HDR is a DIN rail power supply series with ultra slim appearance and full range AC input (100-240Vac). The series
conforms to EN6100-3-2, the norm the European Union regulates for harmonic current. With plastic housing, it can
effectively prevent user from electric hazards. Like other Mean Well’s DIN series, they can be mounted on a TS35
Standard DIN rail.
Installation
(
1
)
Always allow good ventilation clearances, 5mm left and right, 40mm above and 20mm below, around the unit
in use to prevent it from overheating. Also a 10-15 cm clearance must be kept when the adjacent device is a
heat source.
(
2
)
The appropriate mounting orientation for the unit is vertical, the input terminals at the bottom and output on
the top. Mounting orientations other than that, such as upside down, horizontal, or table-top mounting, is not
allowed.