Chapter 4 Operation of Compressor and Unit
Compound 2-stage Screw Compressor 2016**C
4.2 Precautions for Operation
4-6
4.2.3 Actions for Stopping the Compressor for Long Period of Time
Before stopping the compressor for a long time, make sure to perform the following steps.
Turn off the motor main power.
Turn off the oil heater power and the control power.
Close the suction stop valve and discharge stop valve.
If the operation stop period is 1 month or longer, perform the following checks once per month.
Measure the system pressure.
Check for refrigerant leak.
Operate the oil pump for 5 minutes. After that, rotate the compressor shaft (10 rotations or
more).
When restarting the compressor after an operation stop period of 1 year or longer, check the system for
refrigerant leak and replace the refrigerant oil. Also check the motor insulation resistance.
Supply power to the oil heater at least 1 hour before operation start. Before starting the operation,
confirm that the refrigerant is not condensed in the package by checking the package temperature and
pressure.