2200M4JE-HO-iS2-N_2014.04.
Chapter 1 Safety
Screw Compressor i-series
1.4
Safety Devices
1-7
1.4.3 Compressor Protective Devices
Be sure to adjust the set values and check operation of the protective devices when
commissioning. Also, after that, the regular operation confirmation is necessary.
Install necessary protection devices shown in section 2.3.3 "Alarm Set Values" in this manual chapter 2.
Also, install the following protection devices that are not indicate in section 2.3.3, as occasion
demands.
Protection from motor over current (OCR)
This device activates and applies appropriate control when the current equal to or higher than the
set level flows. In some cases, this device stops the compressor operation.
For more information about setting and installation of this device, please refer to the instruction
manual of the motor.
Protection from oil level decrease
In case of the oil supply by differential pressure, install a protection device to the oil separator for
protect form oil level decrease. Since there is a possibility that alarm for protection from lubricating
differential pressure decrease does not activate even if the amount of lubricant is insufficient.
No
Water
Alarm
If you use water cooling oil cooler and/or water cooling condenser, a suspension of water supply
protection is necessary.
For more information about setting and installation of this protection device, please refer to the
instruction manual of the motor or the like used in the cooling water system.
In the operation test, check that alarms and switches operate normally by using
devices such as pressure tester. Do not operate the compressor with all the valves
closed, or in any other dangerous conditions.
If the protection from oil pressure (OP) or high pressure (HP) activates, do not restart
operation until the cause of activation is removed.