Here is an abbreviated example of a test log dump: 
 

CMD>dump        tests 
 
 
 
 
Final settings will be displayed next. 
If you wish to save to a file, enable text capture now. 
Do not forget to stop capture after data is transferred. 
Press Enter when ready... 
 
 
***********< TEST LOGS >*********** 
 
1/75       MONTHLY 
09/20/19 17:43 
DURATION : 5 MIN 
FAULTS   : 0 
VOUT     : 125.3 
IOUT     : 7.5 
TEMP     : 33.5 deg C 
 

:     :      :      :       

 
75/75       MONTHLY 
03/15/14 08:30 
DURATION : 5 MIN 
FAULTS   : 0 
VOUT     : 126.2 
IOUT     : 6.4 
TEMP     : 26.3 deg C 
 
 
 
 
CMD> 

 
These log each of the times that the inverter ran self-test (which tests the battery and inverter 
operation 

– the primary goal is to make sure that the battery does not yet need to be replaced). 

Again, there is space for up to 75 logs. The first line of a log entry will indicate whether the self-
test was an automated monthly self-test (

MONTHLY

), or an automated yearly self-test (

YEARLY

). The 

rest of the entry will tell you the timestamp of the self-test, the duration of the test (in minutes), 
whether or not faults were detected, the output voltage (in Volts) and current (in Amps) of the 
inverter during the test, and the ambient internal temperature inside the cabinet (in degrees 
Celsius). 
 
Finally, the event log (which also has up to 75 entries) will store the results of manually evoked 
self-test events (

EVENT

). The entries will have the exact same format as the test log, but instead of 

MONTHLY

 or 

YEARLY

, it will say 

EVENT

 
 

 

 

Summary of Contents for E Series

Page 1: ...114063D RS 232 User s Manual RS 232 Communications Series E IE and Series EM Users Manual ...

Page 2: ...reen 5 Version 5 Alarm Setpoint 5 Meter Functions 6 Status 6 Alarms 7 Alarms Events and Tests Dump 8 Date and Time 10 LOCATION OF THE RS232 PORT FOR E IE 6 16 7k 11 LOCATION OF THE RS232 PORT FOR E IE 1 5 5 0k 11 LOCATION OF THE RS232 PORT FOR EM 1 0 2 8k 12 The ZOOM Modem Optional 15 Configuring the ZOOM Modem optional 15 Dialing the ZOOM Modem 15 ...

Page 3: ...ral Inverters CONNECTION The Central Inverter has a 9 pin Sub D DB9 female connector typically located on the back inside of the front display panel located on the door of the inverter See below for the exact location of the connector The connection between the Client and the Inverter is a straight through connection Do not use a Null Modem Cable that flips pins 2 and 3 Pin 2 and Pin 3 are the Dat...

Page 4: ... the inverter is not in shell mode it will not echo back characters you type even though it is indeed receiving them To see what you are typing when the inverter is not in shell mode turn on the local echo setting on your terminal emulator When the inverter is in shell mode it will echo back characters you type You will want to turn off the local echo setting on your terminal emulator or you will ...

Page 5: ...are is available by the ver command CMD ver IF 2 08 FP 1 02 CMD Alarm Setpoint When the set point command is entered the following data is displayed CMD setpoint lvac 108 0 off hvac 132 0 off nlbatt 111 0 off lbatt 105 0 off htemp 45 0 on lrc 0 0 off lvac is the Low Voltage AC alarm hvac is the High Voltage AC alarm nlbatt is the Near Low Battery Voltage alarm lbatt is the Low Battery Voltage Alar...

Page 6: ...n Volts iout is the output current of the inverter current consumed by the load in Amps vbatt is the voltage of the battery in Volts ibatt is the current through the battery in Amps tbatt is not currently supported in hardware Ignore this value for now it is meaningless tint is the ambient temperature inside the inverter cabinet in degrees Celsius To convert to degrees Fahrenheit subtract 32 then ...

Page 7: ... indicates an issue with the output such as a short circuit The Overload alarm indicates too much load above the rating of the inverter on the output The Overload Shutdown alarm indicates that the load is so high above the rating of the inverter that the inverter has shutdown to protect itself The High Ambient alarm indicates excessively high temperature inside the inverter cabinet The High VAC al...

Page 8: ...xt capture now Do not forget to stop capture after data is transferred Press Enter when ready ALARM LOGS 1 75 UTILITY 09 20 19 17 49 END 09 20 19 17 49 2 75 UTILITY 02 11 19 12 52 END 02 11 19 12 52 3 75 UTILITY 11 29 18 13 36 END 11 29 18 13 36 4 75 UTILITY 09 11 18 12 41 END 09 11 18 12 54 74 75 LOAD REDUCTION 07 25 16 13 58 END 07 25 16 13 58 75 75 LOAD REDUCTION 07 25 16 13 58 END 07 25 16 13 ...

Page 9: ...l is to make sure that the battery does not yet need to be replaced Again there is space for up to 75 logs The first line of a log entry will indicate whether the self test was an automated monthly self test MONTHLY or an automated yearly self test YEARLY The rest of the entry will tell you the timestamp of the self test the duration of the test in minutes whether or not faults were detected the o...

Page 10: ... dt command then press the tab key then type the parameter number press tab again then type the new value you wish to set the parameter to and finally press enter Note The inverter does not support Daylight Savings Time If you set the inverter date and time during daylight savings note that logged timestamps during non daylight saving times i e winter will be one hour ahead of the actual time beca...

Page 11: ...114063D RS 232 User s Manual LOCATION OF THE RS232 PORT FOR E IE 6 16 7K LOCATION OF THE RS232 PORT FOR E IE 1 5 5 0K PHONE LINE HOOKUP FOR E MAIL MODEM OPTION PHONE LINE HOOKUP FOR E MAIL MODEM OPTION ...

Page 12: ...114063D RS 232 User s Manual LOCATION OF THE RS232 PORT FOR EM 1 0 2 8K PHONE LINE HOOKUP FOR E MAIL MODEM OPTION RS232 PORT BEHIND FRONT PANEL ...

Page 13: ...114063D RS 232 User s Manual ...

Page 14: ...114063D RS 232 User s Manual ...

Page 15: ...unication by typing AT enter until the message OK appears Type the following AT commands ATM1 enter speaker on until connected AT D0 enter ignore DTR AT K0 enter no flow control ATS0 1 enter auto answer after one ring AT W0 store to non volatile memory Dialing the ZOOM Modem Type AT enter until the message OK appears Type for example ATD9 16109545224 enter ATD is the command 9 16109545224 is the p...

Reviews: