8
115159H - LV I/O OPTION
Other Output Functions:
Input Active, Switched Output, and Transfer Delay
are other functions
available for the output contacts. If an output is set to
Input Active
, it will be
powered as long as the same number input is powered. For example, if input 1
is powered with a 90-277Vac signal, output 1 will be powered.
An output set to
Switched Output
will be powered when the
corresponding input is powered, or when the Series LV unit goes into emergency
backup.
Note:
The output is automatically set to Switched Output when an input is
defined with the Switched Output function.
Transfer Delay
operates as a normally on output and will force a time
delay off of 6 seconds each time the unit transfers to battery. After the delay, the
relay will go back to a normally on state. This function is used with certain
lighting controls that require a break in power for several seconds between
normal power and battery power to detect that the inverter is in emergency
mode.