background image

INSTALLATION

2/4

OUTSIDE THE LUMINAIRE

LED test switch

LVU

-2/5

One 7/8" (22mm) hole with conduit
connector for 184600. 

1.  SPECIFICATION OF LVU-2/5

LVU-2/5 SPECIFICATION

  

2.  INSTALLING THE LVU-2/5

       The LVU-2/5 can be mounted inside or outside (nearby or on top of) the luminaire. 

  

3.  INSTALLING THE LED TEST SWITCH (LTS)

       Select a convenient location for the LTS so that it can be seen after installation. 
       Drill a 1/2"(12 mm) hole for mounting the LTS. Connect the wires from LTS to the 
       LVU-2/5 model according to the wiring diagram on page 3. 

INSIDE THE LUMINAIRE

LVU

-2/5

LED test switch

CAUTION: MAKE CERTAIN THE AC POWER IS OFF AND THE LVU-2/5 UNIT CONNECTOR IS 
                    DISCONNECTED UNTIL THE INSTALLATION IS COMPLETE.

LVU-2

LVU-5

Output 

Output Power

 Voltage

Model

Input 

277V/50Hz

120V/60Hz

25W 

50W

277V/60Hz

120V/60Hz

WWW.MYERSEPS.COM

Summary of Contents for LVU-2

Page 1: ...al power emergency power unit and connector of this product before servicing 5 For emergency operation of LED incandescent fluorescent and screw base lamps 6 Use this product in 0 C minimum 50 C maximum ambient temperatures Ta To ensure the emergency operating time over 90 minutes the output emergency power of LVU 2 5 should be maximum of 25W for the LVU 2 and 50W for the LVU 5 7 Use with grounded ...

Page 2: ...TS Select a convenient location for the LTS so that it can be seen after installation Drill a 1 2 12 mm hole for mounting the LTS Connect the wires from LTS to the LVU 2 5 model according to the wiring diagram on page 3 INSIDE THE LUMINAIRE LVU 2 5 LED test switch CAUTION MAKE CERTAIN THE AC POWER IS OFF AND THE LVU 2 5 UNIT CONNECTOR IS DISCONNECTED UNTIL THE INSTALLATION IS COMPLETE LVU 2 LVU 5 ...

Page 3: ...ORESCENT INCANDESCENT LUMINAIRE DIM IN BLUE WHITE DIM IN BLUE RED 0 10V DIMMER GRAY OUT NEUTRAL VIOLET VIOLET UNIT CONNECTOR WIRING DIAGRAM FOR 1 10V DIMMABLE EMERGENCY LIGHTING SYSTEM LVU 2 5 TOTAL DIMMABLE POWER LVU 2 UP TO 175W WHITE RED BLACK YELLOW GREEN WHITE BLACK ANY QUANTITY DIM OUT BLUE DIM OUT BROWN ORANGE OUT HOT NEUTRAL GROUND SWITCH HOT LED Test Switch 120 277 VAC 120 277 VAC LED FLU...

Page 4: ...ed on 3 Monthly Auto Test Monthly Auto Test should be executed every 30 days and to test If the switchover of normal and emergency mode is normal If the emergency function and battery s charging and discharging condition is normal Auto Test time is about 30 seconds 4 Annual Auto Test Annual Auto Test will be executed every 52 weeks after 24 hours full charging and to test If the battery s voltage ...

Reviews: