Protection Relay Settings
2
6
The Mode Selector Switch may be LOTO’d when rotated counter clockwise (CCW) to
Repair Service Mode.
Mode Descriptions:
1. Automatic Mode
All Protection logic and reclosing (if configured) is enabled and all programmed
commands for TRIP and CLOSE are allowed
By pushbutton or SCADA, the Protection Relay can 3-Phase TRIP
By pushbutton or SCADA, the Protection Relay can 3-Phase CLOSE
The Protection Relay cannot be commanded (via pushbutton or SCADA) to 1-
Phase TRIP or 1-Phase CLOSE
2. Repair Service Mode
All Protection logic and reclosing (if configured) is enabled, however CLOSE
commands are DISABLED… TRIP commands are ALLOWED
By pushbutton or SCADA, the Protection Relay can 3-Phase TRIP
Only by pushbutton, the Protection Relay cannot 3-Phase CLOSE
Only by pushbutton, the Protection Relay can 3-Phase CLOSE
By pushbutton or SCADA, the Protection Relay can 1-Phase TRIP
Only by pushbutton, the Protection Relay can 1-Phase CLOSE
Power Supply & UPS Battery TRIP
The myPV ClearSky’s SEL-751 is pre-programmed to support TRIP on-alarm-
condition for the following conditions and time delays:
On loss-of-control-power, when the N.O. power supply digital output OPENs, the
Protection Relay will TRIP after 30 seconds.
On UPS-battery-alarm, when the N.O. UPS digital output OPENs, the Protection
Relay will TRIP after 40 minutes.
Summary of Contents for ClearSky
Page 1: ...myPV ClearSky User Manual 1 myPV ClearSky User Manual ...
Page 12: ...Resources 12 ...
Page 14: ...Resources 14 ...
Page 19: ...Resources 19 ...
Page 20: ...Resources 20 ...
Page 48: ...Pre Energization Checks 48 Control Panel Verification Locations ...
Page 55: ...Initial Energization 55 ...
Page 63: ...Operational Testing 63 The myPV ClearSky may be left in this condition indefinitely ...
Page 68: ...Spare Parts 68 ...
Page 69: ...Spare Parts 69 ...