Troubleshooting
7
2
Following a TRIP event, the Protection Relay will not allow a CLOSE command if the
TRIP has net been cleared. An uncleared TRIP event will cause the Red TRIP indicator
to illuminate.
To clear the TRIP event, press the TARGET RESET until the Red TRIP indicator is no
longer illuminated.
TRIP Indicator NOT Illuminated
MV Breaker TRIP on CLOSE
If the MV Breaker immediately TRIPs following a CLOSE, the Protection Relay is
commanding it to TRIP due to a protection element or logic driven fault detection.
Consult the Protection Relays event files to determine the cause of the TRIP command.
MV Breaker Will Not CLOSE