11
Table 3-3 Settings in the System Menu – Cont.
cfgname
<filename>
Enters the name (max. 32 characters)
under which the 608MFX configuration is
loaded or stored as a file on the TFTP
server. Depending on the configuration of
the TFTP server, this may also include
further path names.
Administrator only
cfgsave
Stores the 608MFX configuration as a file
on the TFTP server.
cfgload
Loads the 608MFX configuration as a file
from the TFTP server.
Administrator only
logname
<file name>
Enters the name (max. 32 characters)
under which the 608MFX log is stored as
a file on the TFTP server. Depending on
the configuration of the TFTP server, this
may also include further path names.
Administrator only
logsave
Saves the 608MFX log as a file on the
TFTP server.
Administrator only
Note:
The protected settings are as follows: IP Address, Subnet Mask, Default
Gateway, Port Name, System Name, System Location, System Contact. These
settings are unaffected by restoring factory defaults (memreset).
OSM/ESM Menu
This menu includes special Optical Systems Module (OSM) and Electrical Systems
Module (ESM) 608MFX settings (i.e. setting the fault mask).
Table 3–4 Settings in the OSM/ESM Menu
Command
Description
Comment
info
Displays the current values of
the 608MFX setting.
link <E | D> [ports]
Enable | Disable link
monitoring.
Administrator only
Link monitoring is
part of the fault mask
of the 608MFX. The
signaling contact and
the fault LED of the
608MFX are activated
when a port whose
link monitoring is
activated has no valid
link.