(Revised 2012-05-01
Page 14 of 170
APPLYING POWER (Top View)
•
Unscrew & Remove the DC Voltage Input
Plug from the Power Input Header
•
Install the DC Power Cables into the Plug
(observing polarity).
•
Plug the Voltage Input Plug back into the
Power Input Header.
•
Tightening torque for the terminal block
power plug is 0.5 Nm/0.368 Pound Foot.
•
Verify the Power LED stays ON (GREEN).
Notes:
•
Only 1 power supply must be connected to power for minimal operation. For redundant power
operation, V
1
and V
2
inputs must be connected to separate DC Voltage sources. This device will
draw current from both sources simultaneously. Use 16-28 gauge wire when connecting to the
power supply.
•
The Fault pins on the power connector can be used for an alarm contact. The current carrying
capacity is 1A at 24VDC. It is normally open and the relay closes when a fault condition occurs.
These pins can be used to connect an external warning device such as a light in order to provide an
external alarm. The conditions for generating a fault condition (closing the relay) can be configured
through software.
Recommended 24V DC Power Supplies, similar to: N-Tron’s P/N NTPS-24-1.3 (NOTE: Not appropriate
for use with M12, POE, and HV models.):
•
Input AC 115/230V
•
Output DC 24-28V
•
Output Current 1.3A @ 24V
1.0A @ 28V
•
Power 30W
•
35 mm DIN-Rail Mountable
•
Dimensions: 45X75X91 mm
Summary of Contents for 710FX2 Series
Page 1: ...710FX2 Managed Industrial Ethernet Switch User Manual Installation Guide ...
Page 11: ... Revised 2012 05 01 Page 11 of 170 CLEANING Clean only with a damp cloth ...
Page 33: ... Revised 2012 05 01 Page 33 of 170 Administration SNMP Continued ...
Page 37: ... Revised 2012 05 01 Page 37 of 170 DHCP Server Setup Profiles Continued ...
Page 46: ... Revised 2012 05 01 Page 46 of 170 DHCP Relay Local IP Setup Continued ...
Page 52: ... Revised 2012 05 01 Page 52 of 170 Ports Configuration Continued ...
Page 83: ... Revised 2012 05 01 Page 83 of 170 The user can specify the manual router ports ...
Page 86: ... Revised 2012 05 01 Page 86 of 170 IGMP RFilter Continued Modifying rfilter port settings ...
Page 94: ... Revised 2012 05 01 Page 94 of 170 N Ring Advanced Configuration Continued ...
Page 119: ... Revised 2012 05 01 Page 119 of 170 If a Configuration Device is present that is presented ...