(Revised 2012-05-01)
Page 14 of 163
APPLYING POWER (Top View)
•
Unscrew & Remove the DC Voltage Input
Plug from the Power Input Header
•
Install the DC Power Cables into the Plug
(observing polarity).
•
Plug the Voltage Input Plug back into the
Power Input Header.
•
Tightening torque for the terminal block
power plug is 0.5 Nm/0.368 Pound Foot.
•
Verify the Power LED stays ON (GREEN).
Notes:
•
Only 1 power supply must be connected to power for minimal operation. For redundant power
operation, V
1
and V
2
inputs must be connected to separate DC Voltage sources. This device will
draw current from both sources simultaneously. Use 16-28 gauge wire when connecting to the
power supply.
•
The Fault pins on the power connector can be used for an alarm contact. The current carrying
capacity is 1A at 24VDC. It is normally open and the relay closes when a fault condition occurs.
These pins can be used to connect an external warning device such as a light in order to provide an
external alarm. The conditions for generating a fault condition (closing the relay) can be configured
through software.
Recommended 24V DC Power Supplies, similar to: N-Tron’s P/N NTPS-24-1.3 (NOTE: Not appropriate
for use with M12, POE, and HV models.):
•
Input AC 115/230V
•
Output DC 24-28V
•
Output Current 1.3A @ 24V
1.0A @ 28V
•
Power 30W
•
35 mm DIN-Rail Mountable
•
Dimensions: 45X75X91 mm
Summary of Contents for 712FX4 Series
Page 1: ...712FX4 Managed Industrial Ethernet Switch User Manual Installation Guide...
Page 11: ...Revised 2012 05 01 Page 11 of 163 CLEANING Clean only with a damp cloth...
Page 33: ...Revised 2012 05 01 Page 33 of 163 Administration SNMP Continued...
Page 37: ...Revised 2012 05 01 Page 37 of 163 DHCP Server Setup Profiles Continued...
Page 40: ...Revised 2012 05 01 Page 40 of 163 DHCP Server Setup IP Maps Continued...
Page 46: ...Revised 2012 05 01 Page 46 of 163 DHCP Relay Local IP Setup Continued...
Page 52: ...Revised 2012 05 01 Page 52 of 163 Ports Configuration Continued...
Page 82: ...Revised 2012 05 01 Page 82 of 163 IGMP RFilter Continued Modifying rfilter port settings...
Page 90: ...Revised 2012 05 01 Page 90 of 163 N Ring Advanced Configuration Continued...
Page 113: ...Revised 2012 05 01 Page 113 of 163 If a Configuration Device is present that is presented...
Page 149: ...Revised 2012 05 01 Page 149 of 163...