N1C L-Series(1-3kVA) UPS
User Manual
3 Installation
21
The construction of installation place should have been finished and the floor has been hardened.
The installation place should be clean and without dust.
Installation environment requirements
Operating temperature: 0
℃~
+60
℃
;
Relative humidity: 0%RH
~
95%RH, with no condensation;
Cooling way: air-cooling;
Operating altitude: meet GB3859.2-93 requirements;
Verticality: without vibration and the vertical gradient should be not more than 5º;
Pollution grade: grade
Ⅱ
.
UPS should be installed in the place where is with good ventilation, proper temperature and humidity,
and without dust. The recommend environment temperature is 20~25
℃
and humidity is about 50%.
Don't install UPS in the place with metal conductive dust. UPS is only suitable to use in the non-tropical
climate conditions.
3.2.2 Input Breaker Selection
Add a breaker or a power distribution box in the input wire of UPS, which matches with the power of
UPS, to isolate the mains. Consider the charging power of UPS and the transient current impact when
power on, the current of the selected breaker should be 1.5
~
2 times of the max. input current of UPS.
Besides, the selected breaker should be without the power leakage protection to avoid maloperation.
The distribution box is better to be made by the professional company. The selection of input breaker
refers to Table3-1.
Table3-1
The recommended input breaker of N1C series(1-3kVA) UPS
Model
AC input
Max. current(A)
Recommended breaker(A)
N1C.L1000
12
20
N1C.L2000
24
32