3 Installation
N1C L-Series(1-3kVA) UPS
User Manual
22
Model
AC input
Max. current(A)
Recommended breaker(A)
N1C.L2200
26
32
N1C.L3000
36
50
N1C.L2000G
12
20
N1C.L2200G
12
20
N1C.L3000G
18
32
3.2.3 Selection of the Cross Sectional Area of Wire
For the selection of the cross-sectional area of AC input wire, AC output wire and battery wire of N1C
L-Series(1-3kVA) UPS, please refer to Table3-2 for the corresponding recommended value and choose
upwards.
Table3-2
The recommended cross-sectional area of wire
Cross-sectional area(mm
2
)
1
1.5
2.5
4
6
10
16
25
Ampacity(A)
Rubber
(25
℃
)
8
12
20
28
42
70
96
125
Plastic
(25
℃
)
6
9
15
20
30
50
64
100
The equipped wires are with good quality and meet safety requirements, which pass international
authentication and UL authentication. If user prepares wires by themselves, please refers to the
recommended cross-sectional area of wire that is about 5m length listed in Table3-2. Longer wires
require larger cross-sectional areas.
3.3 Unpacking and Checking
Unpacking UPS and conduct the following items:
Inspect the appearance for shipping damage. If any shipping damage is found, report it to the
carrier immediately.