N1C L-Series(1-3kVA) UPS
User Manual
A Technical Specifications
43
Model
Index
N1C.L2000G
N1C.L2200G
N1C.L3000G
Transfer time
between battery mode
and mains mode(ms)
0
O
v
er
lo
ad
a
b
ility
Low
overload for
1min
2000VA/1800W
<
Load
≤
2600VA/2080W
2200VA/1980W
<
Load
≤
2860VA/2080W
3000VA/2700W
<
Load
≤
3900VA/3120W
Medium
overload for
1s
2600VA/2080W
<
Load
≤
3000VA/2400W
2860VA/2080W
<
Load
≤
3300VA/2080W
3900VA/3120W
<
Load
≤
4500VA/3600W
High
overload for
200ms
3000VA/2400W
<
Load 3300VA/2080W
<
Load
4500VA/3600W
<
Load
Output receptacles
One IEC C19 socket with 16A and six IEC C13 sockets with 10A
O
th
er
f
eat
u
res
Backup time
11 mins
Charge recovery time
Depend on battery capacity
Communication
interface
Standard: SNMP adapter and USB port support UPS power management
software;
Optional: RS485 and dry contact.
Display
LCD displays the running status of UPS.
Alarm function
Battery low-voltage, mains abnormal, UPS fault, output overload
Protection function
Battery under-voltage protection, overload protection, short-circuit protection,
over-temperature protection, input over-voltage protection
Noise(dB)
<55
Working temperature
(
℃
)
0
~
60