NE Series (20-30kVA)
User Manual
Chapter 3 Installation
Table3-1 Selection for input cables
Power
(
kVA
)
Current
(
A
)
Live
wire
cross-section
area
(
mm²
)
Neutral wire
cross-section
area
(
mm²
)
Grounding wire
cross-section
area
(
mm²
)
20
68
16
16
10
30
102
25
25
16
Table3-2 Selection for output cables
Power
(
kVA
)
Current
(
A
)
Live wire
cross-section
area
(
mm²
)
Neutral wire
cross-section
area
(
mm²
)
Grounding wire
cross-section
area
(
mm²
)
20
61
16
16
10
30
91
25
25
16
Table3-3 Selection for battery cables
Power
(
kVA
)
Battery
quantity
Max. current
(
A
)
Wire cross-section area
(
mm
2
)
20
16
113
25
30
16
170
35
The cross-sectional area listed in Table3-1, Table3-2 and Table3-3 is recommended cables cross-
section area for 5 m long lines. Longer lines require larger cross-sectional areas.
3.6 Surge Protection
If the UPS is installed in a lightning-prone area, install multiple surge protection devices between the
power grid and the UPS. The UPS installed outdoors requires a higher surge protection level than those
installed indoors.