A Technical Specifications
Model
Items
NE20L/NE20PL
NE30L/NE30PL
Cooling way
Forced air cooling
Operation temperature (
℃
) 0-40º
Storage temperature
-25
℃
~+55
℃
. If the transporting and storage temperature exceed the work
temperature, it is necessary to place the UPS to normal operation
temperature environment and keep it for at least 4 hours before installing
and powering on.
Altitude
The altitude should be no more than 1500 m, or it needs to decrease the
capacity according to GB/T 3859.2 to use.
Relative humidity
0~95%, with no condensation
Size (mm) (W×D×H)
500×800×1 500
Net weight
(
kg
)