GT1175 Slide Door Opus Control Wiring and Programming Manual

Rev. 8-11-21 

P/N C-00391

SECTION 8.5: Input Settings

Input Setting

Parameter

Terminal

Default

Range

Description

Input 62 Setting

Terminal 4 Ext Activation

— — 

No input

Input SWL Setting Terminal 6 Sidelite Safety

All Mode Activation

Activates in all modes but OFF

Input H Setting

Terminal 10 Reduced Open

Interior Activation

Interior Activation (works in one-way)

Input SQ Setting 

(rev 28 and later)

Terminal 9 Sequential Input

Exterior Activation

Activation on exterior

Beam Sensor

Threshold sensor (slide door only)

LE Approach Sensor

Door-mounted Sensor on approach side

Unlock Input

For Lock Feedback where applicable

Disable Power Close

Turns off power close and hold close

Sequential Input

Takes one activation to open door and

another to close door

Open Slow

Causes slow opening of the door

Safety with Lockout

Swing side header mounted sensor input 

(swing door only)

Continuous Safety

Door-mounted Sensor on pull side

Reduced Opening

Causes unit to change to reduced open

Emergency Close

 

and Lock

Forces the door to slowly close and lock 

 

(if equipped)

Hold Open Mode

Holds door in open position

Asia Only

(Do Not Use)

ANSI 

does not allow

 Activation Sensor to 

be mounted on the swing side of door. 

If activated, Opus will ignore the Activation 

Sensor while d-oor is moving.

This input is for the 

ASIAN market ONLY

AsiaSpec_IntActSwgSd

AsiaSpec_ExtActSwgSd

Input 62 Timer

N/A

Same as Open Timer Same as Open Timer

0 thru 10, 12,15, 20, 25 sec

Hold open time for Input 62

Input H Timer

N/A

Same as Open Timer 0 thru 10, 12,15, 20, 25 sec Hold open time for Input H

Input SWL Timer

N/A

Same as Open Timer Same as Open Timer

0 thru 10, 12,15, 20, 25 sec

Hold open time for Input SWL

Input SQ Timer

N/A

Same as Open Timer Same as Open Timer

0 thru 10, 12,15, 20, 25 sec

Hold open time for Input SQ

Input 61 Circuit

N/A

Normally Open

Normally Open

Normally Close

Circuit logic for Input 61

Input 62 Circuit

N/A

Normally Open

Normally Open

Normally Close

Circuit logic for Input 62

Input 6B Circuit

N/A

Normally Open

Normally Open

Normally Close

Circuit logic for Input 6B

Input 

 

SWL Circuit

N/A

Normally Open

Normally Open

Normally Close

Circuit logic for Input SWL

Input BA Circuit

N/A

Normally Close

Normally Open

Normally Close

Circuit logic for Input BA

6B Stop Closing

N/A

No

Yes

No

While closing and 6B is ON at latch check, cycle 

Determines door movement stop or close.

After 6B Open?

N/A

Yes

Yes

No

Determines door movement open or close, 

after 6B.

Summary of Contents for GYRO TECH GT-1175

Page 1: ...into the myNABCO portal 4 SECTION 2 4 QR Code Links 4 CHAPTER 3 GETTING STARTED 4 SECTION 3 1 Features 4 SECTION 3 2 Wiring 5 SECTION 3 3 General Specifications 5 SECTION 3 4 Electrical Specifications...

Page 2: ...LIDE DOOR WIRING DIAGRAMS 19 SECTION 11 1 Single Slide Door with Acusensor M and Holding Beam w monitoring 19 SECTION 11 2 Telescopic Slide Door with Acusensor M and Holding Beam w monitoring 20 SECTI...

Page 3: ...t all power to the junction box prior to making any electrical connections Failure to do so may result in serious personal or fatal injury When uncertain whether power supply is disconnected always ve...

Page 4: ...ting sliding doors using U01 U19 controls Contact Customer Service at 1 888 679 3319 to purchase Retrofit kits SECTION 2 3 Request a User Name Password to gain access into the myNABCO portal To gain a...

Page 5: ...O factory utilizes Underwriters Laboratories UL recognized component wire terminals and connector housings to manufacture all Automatic Door systems Table 1 Power Draw Common Accessories Sensor Part N...

Page 6: ...2 clicks to advance through each menu item Clockwise To scroll forward through screens and programming options Counterclockwise To scroll backward through screens and programming options DN 2429 Type...

Page 7: ...Range Open Timer Reac on Power Open Recycle Sens Close Recycle Sens A er Open Recycle Op onal Se ng Hold Close Force Power Close Range Manual Open Func on Manual Open Sens Manual Open Timer BCHK Lock...

Page 8: ...ions Displays the current status of all of the Input Output lines of the terminal strip SECTION 4 2 Level Two Access Screen Note The Activate Passcode option is only displayed in the event 0045 had no...

Page 9: ...g History Data LEVEL 3 Low Energy or Full Low Full Rotate Dial LEVEL 4 LEVEL 2 Long Push Long Push CHAPTER 5 STROKE LEARNING DN 2314 11 20 10 12 Type 1 GT1175 Opus Slide Status Slow Closing Error Ac v...

Page 10: ...at the top Opus Controls are labeled Type 1 or Type 2 Type 1 should be considered the Slave Control Type 2 should be considered the Master Control X All Activation Devices and main harness are connect...

Page 11: ...ta SimPair Yes No 11 20 10 12 Type 2 GT1175 Opus Slide Status Fully Closed Error Ac va on IN EXT Posi on Other BA 6B SWL Push and Hold Dial Go to Se ng Mode Figure 8 Reset Control 2 Turn the Rotary Di...

Page 12: ...d ATTENTION Bi Parts are set up as Left Hand Left Right Left From the Exterior Side of Building determine which Handing to enter Left or Right RIGHT HANDING DN 1326 LEFT HANDING EXTERIOR SIDE OF BUILD...

Page 13: ...ormal Sim Pair If selected before returning to last screen option to copy settings to other Control is given Double Egress The Activation signal only is shared between doors All other signals are inde...

Page 14: ...nality N C Air lock Set for Air lock functionality Breakout Pass through Output closes when breakout occurs TrmnL H PassThrough Output changes state when input H changes state Door Sequencing Provisio...

Page 15: ...ds door in open position Asia Only Do Not Use ANSI does not allow Activation Sensor to be mounted on the swing side of door If activated Opus will ignore the Activation Sensor while d oor is moving Th...

Page 16: ...ettings are OFF by default except when used as 1175 Opus Slide in which case standard settings have monitoring enabled SECTION 8 6 History Setting History Data Parameter Description Operation Cnt Indi...

Page 17: ...justment 11 20 10 12 Short Push Rotary Dial SECTION 9 2 Recycle Count Reset Opera on Cnt 0 cnt Open Recycle Cnt 0 cnt Close Recycle Cnt 0 cnt Latest Rcycl Posi on C1 0 Op 0 Clear Recycle Cnt 0 If you...

Page 18: ...eep sufficient spacing between high voltage and low voltage wiring 120 VAC Power wires must be routed separate from other wiring located near the top of inside Header Ensure that incomming electrical...

Page 19: ...40 P N M 01070 15 Breakout Jumper P N A 00385 BROWN GREY BLACK WHITE YELLOW RED GREEN BLUE ACUSENSOR M HARNESS P N A 01292 INTERIOR ACUSENSOR M P N V 00741 EXTERIOR ACUSENSOR M P N V 00741 OPTEX Hold...

Page 20: ...eakout Jumper P N A 00385 BROWN GREY BLACK WHITE YELLOW RED GREEN BLUE ACUSENSOR M HARNESS P N A 01292 INTERIOR ACUSENSOR M P N V 00741 EXTERIOR ACUSENSOR M P N V 00741 OPTEX Holding Beam Controller P...

Page 21: ...at the NABCO Factory Check to ensure both Opus Controls are programmed Under Op onal Se ngs Sim Pair Se ng is set to Normal Sim Pair For each Opus Control perform Stroke Learn Opus Control Types Type...

Page 22: ...Terminal 3 4 Breakout connector is removed from main harness and blue wires are connected diretly to the breakout beam control OTHER WIRING NOT SHOWN FOR SIMPLICITY BLUE GREEN ORANGE ORG WHT RED BROW...

Page 23: ...P N M 02043 Breakout Switch P N A 00758 Full Open P N A 00387 Fixed Sidelite BN BK Y RD Rocker Switch Extension 36 P N A 00967 BN BK Y RD Sensor 12 VD Ac va on Monitoring Common Control Main Harness B...

Page 24: ...N A 01192 ACUSENSOR M P N V 00741 NOTES ON AN 1175 INPUT SWL IS SET TO SLOW OPEN BY DEFAULT IN THIS CASE THE DOOR WILL OPEN SLOWLY WHEN ACTIVATED DURING SIDELITE DETECTION IF INPUT SWL IS SET TO CONT...

Page 25: ...RELAY OUTPUT 3 ELECTRIC STRIKE LOCK OUTPUT TIMER 1 5 1 5 seconds OPUS Assembly Single P N A 01418 Telescopic P N A 01420 GREEN Ground Power Switch OPUS Power Connector 1175 OPUS Electric Lock Harness...

Page 26: ...TPUT TIMER 1 5 1 5 seconds BLACK Hot WHITE Neutral GREEN Ground OPUS Power Connector WHITE WHITE BLACK BLACK 1175 OPUS Electric Lock Harness Set P N M 02044 Power Supply P N V 00022 Magne c Lock GREEN...

Page 27: ...r Switches with Key Switches 1 Replace the Rocker Switch with the Key Switch 2 Keep the Key Switch in 2 Way 3 Connect the Remote Switch to the Opus Control Terminals 11 and 14 for 1 Way Terminals 12 a...

Page 28: ...CONTROLLER P N A 00129 Terminal 6 Terminal 1 Power Power Signal Signal Monitor Monitor SET TO MODE B 2 FLASHES 1 2 3 4 6 5 7 8 9 10 12 11 13 14 Optex OS 12C T Controller Terminal 7 Terminal 14 HOLDIN...

Page 29: ...gnal to the door control to hold the door open until the threshold is clear and the beam is restored DN 1879 SINGLE SLIDE DOOR BI PART SLIDE DOOR Emit Rcvr Emit Rcvr Floor 21 inches 54 inches Floor 21...

Page 30: ...atus should now show Fully Closed Must navigate back to the main screen as shown at right for an activation signal to work Hard to manually open door Software Revision up to and including 18 Re enter...

Page 31: ...and adjust the recycle sensitivity and Open Close speed No Load No load error Check operator gear cracked belt skipped Electrical Lock Electrical lock error Check lock settings and wiring Ensure lock...

Reviews: