9.2  试运行 Pilot run 

按  9.1 条各项全部确认无异常情况后,可以进行试运行。 

(1)扳动操作手柄,投入电源。 
(2)断路器主电路带电后,按紧急脱扣按钮,断路器应脱扣,操作手柄处于脱扣位置。如果试运行都能满
足,可投入运行。 

Carry out pilot run after all items in rule 9.1 are assured normal. 

        (1) Pull the operating handle and switch power supply on. 

(2)Press emergency release button after main circuit of the breaker is electrified. Then, the breaker 

should be released and the operating handle is at released position.Operation can be carried out if pilot 
run successes. 

9.3  维护  Maintenance 

 

维护检查必须有专业技术人员负责。 

 

用户如需选用内、外附件,按所订型号由本公司提供,以保证质量。如用户自行选购或改装,本公司
不能负责。 

 

在执行维护操作前,必须先完成下列操作: 

(1)使断路器分闸; 
(2)断开电源与断路器的连接(包括主电路、辅助电路) 
(3)将断路器从安装位置上卸下(一般用于插入式,固定式最好也如此)。 
断路器维护在正常操作条件下每年一次,在非正常条件下每半年一次,以下为维护内容: 
(1)再扣断路器,合、分断路器,在断路器合闸时用脱扣按钮使断路器脱扣,往复操作 5 次,断路器应能可

靠进行再扣、合、分、脱扣动作; 

(2)清除断路器表面及连接处的灰尘(用清洁、干燥的抹布擦拭); 
(3)清洁隔弧板,如必要则需要更换隔弧板; 
(4)检查所有连接情况,用砂布擦除氧化物,用可溶解剂清洁,拧紧螺栓和螺母; 
(5)如果断路器还装有其它内、外部附件,应逐一检查各个附件,以确保其处于正常工作状态。 
(按照 8 附件说明详细内容进行测试) 

 

Maintenance and check should be finished by professional technicians. 

 

To guarantee quality, the company provide internal and external accessories to customer according 
to the subscribed type. The company is free from responsibility if the customer purchases or refits 
internal and external accessories by himself. 

 

The following operations should be finished before maintenance. 

(1)Open the breaker. 
(2)Disconnect power supply and the breaker (including main and auxiliary circuits); 
(3)Uninstall the breaker from the installing position (suitable for insertion type, so as fixation type). 
Maintenance on the breaker should be carried out once every year in normal operation condition or once 
every half a year in an abnormal condition. The followings are included in maintenance. 

Summary of Contents for NDM2 Series

Page 1: ...DT2920016 4 2000 201315 021 68586699 021 23025796 1 24 Shanghai Liangxin Electrical Co Ltd NDM2 NDM2 Series MCCB Product Manual IPD ENG DEV T32 A0 2019 11 05 2020 10 20 2020 10 20 2020 10 20 2020 10 2...

Page 2: ...01315 021 68586699 021 23025796 2 24 3 3 1 Update the technical patameters of project 3 see table 1 for details 20200725 Wang Hu Peng Haoran Hu Qi 4 Change the altitude derating factor 20201020 Wang H...

Page 3: ...ation scope 4 2 Model and implication 4 3 Main technical parameters 7 4 Stand working conditions 9 5 Wiring Method 11 6 Shape dimension Dimension 12 7 Mounting Method 17 8 Accessory 18 9 Application M...

Page 4: ...d and marine use The rated working voltage i s AC 690V with the insulation voltage of 1000V will be suitable for in frequency switching of circuits and starting of motors in 50 60Hz circuit The breake...

Page 5: ...ents motor protection 12 4 N N pole type of four pole product below A N N A N pole is always close without overload release B N N B N pole is open or close together with other three poles and without...

Page 6: ...ps of double auxiliary contact 60 Two groups of single auxiliary contact 61 Double auxiliary contact single auxiliary contact 62 Undervoltage release double auxiliary contact 70 Undervoltage release s...

Page 7: ...echanical life 20000 NDM2 63M 52 5 38 NDM2 63 4P 52 5 38 NDM2X 125 125 35 26 25 380 400 415 16 20 25 32 40 50 63 80 100 125 Electrical life 8000 Mechanical life 20000 NDM2 125C 25 18 75 NDM2 125L 36 2...

Page 8: ...s NDM2 400C 400 35 26 25 100 400 415 50 60 225 250 315 350 400 Electrical life 7500 Mechanical life 10000 NDM2 400L 50 37 5 NDM2 400M 65 48 75 50 50 500 20 15 690 NDM2 400H 100 75 400 415 NDM2 400 4P...

Page 9: ...r 6 Resisting effects by salt mist and oil mist 7 Resisting the effects by mould 8 Installation category for the breaker which is connected to main circuit Installation category for the breaker which...

Page 10: ...2 0 901 0 879 5 630 1 0 979 0 958 0 937 0 915 0 893 0 871 6 800 1 0 980 0 960 0 939 0 918 0 897 0 877 5 table5 Molded Case Circuit Breaker Derating Coefficient Table in High altitude Place m Altitude...

Page 11: ...0 M12 28 M6 6 5 Wiring Method 7 Table 7 of sectional area and applicable rated current adopted in wiring A Rated current A 10 12 5 16 20 25 32 40 50 63 80 100 125 140 160 180 200 225 250 315 350 400 W...

Page 12: ...25796 12 24 6 Shape dimension Dimension 1 2 This product can also be front plate connector wiring on back of the board specific see Figure 1 figure 2 1 Fig 1 Front connection NDM2 63 800 NDM2X 125 2 F...

Page 13: ...H5 79 73 78 H4 54 53 58 Front connection L2 117 132 144 H3 7 7 5 H2 20 5 27 5 24 24 H1 90 5 98 5 86 104 110 127 L1 172 250 291 W2 103 122 142 H 74 81 5 69 87 5 86 103 L 135 150 165 W1 50 60 30 60 70 W...

Page 14: ...ons d 7 7 7 B 194 200 243 A 44 58 70 Dimentions Rear connection H5 82 88 98 H4 42 44 33 Front connection L2 223 6 234 243 H3 9 8 11 5 H2 38 43 40 43 H1 157 159 159 L1 475 488 498 W2 198 240 280 H 106...

Page 15: ...terminal cover Without a terminal cover NDM2 63 25 65 30 30 NDM2 X 125 25 65 30 30 NDM2 250 25 65 30 30 NDM2 400 25 120 35 35 NDM2 630 25 120 35 35 NDM2 800 25 120 35 35 6 2 6 2Minimum center distance...

Page 16: ...t breaker from bottom With a terminal cover Without a terminal cover NDM2 63 90 90 NDM2 X 125 90 91 NDM2 250 90 93 NDM2 400 155 155 NDM2 630 155 155 NDM2 800 155 155 1 2 3 Note 1 Cable insulating conn...

Page 17: ...s carried out on the breaker again 500VDC tramegger When breaker is broken up insulation test is conducted separately between connecting panels 1 2 3 4 5 6 connecting panels 1 3 5 and shell Undervolta...

Page 18: ...ly break the breaker up when power voltage is lower than the rated working voltage of undervoltage tripper by 35 the undervoltage tripper can prevent the breaker from closing when power voltage is hig...

Page 19: ...C400V 0 15 DC220V 8 3 2 8 3 2 Status indicator diagrams of auxiliary and alarm contacts Accessary Name Status of breaker Connection status of circuits Auxiliary contact Breaking or free tripping Closi...

Page 20: ...5 6 The switch cabinet door equipped with rotary handle is closed The handle should be operated freely The breaker should be opened when the handle is at the horizontal position and it should be close...

Page 21: ...onal technicians To guarantee quality the company provide internal and external accessories to customer according to the subscribed type The company is free from responsibility if the customer purchas...

Page 22: ...wire connection base for insertion wire connection of the breaker are fixed on an installation panel 2 Connected to main circuit 2 1 Wiring operation should be carried out by professional technicians...

Page 23: ...r maintenance or exchange should be paid in warranty period if the error is caused by any one of the following reasons 1 Improper use self refit improper maintenance and so on 2 Use out of the standar...

Page 24: ...e a knowledge of technical documents of this product and maker order by an Ordering rule table in accordance with the future practical use of breaker Shanghai Liangxin Electrical CO LTD 2000 No 2000 S...

Reviews: