文件编号:
NDT2920129
文件版本:
2
地址:上海市浦东新区申江南路
2000
号
邮编:
201315
电话:
(021)68586699
传真:
(021)23025796
第
13
页
共
20
页
7.2 安装
Installation
请安装于金属等阻燃物上。断路器可垂直安装,也可以水平安装。
Please install the breaker on flame
retardants such as metal, etc. It can be installed vertically or horizontally.
产品垂直安装时,安装面与垂直面的倾斜角度≤±
22.5
°。
When the product is installed vertically, the angle of
inclination between the installation surface and vertical surface shall be
≤±
22.5
°
.
图
14.1
:垂直安装
图
14.2
:水平安装
Fig.14.1 Vertical installation Fig.14.2 Horizontal installation
8.
附件说明书/ Accessory
8.1 欠电压脱扣器 Under-voltage release
断路器带有欠电压脱扣器时,应使欠电压脱扣器先通电,断路器才允许合闸.
When the breaker has an under-voltage release, the under-voltage release should be
electrified, and then the breaker allows switch on.
根据引出的导线编号借入电源(直流电源不必区分正负极)
Power supply is accessed according to lead-out wire number(anode and cathode of DC power
supply are not differentiated).
当电源电压下降到欠压脱扣器额定工作电压的 70%~35%
范围内时,欠压脱扣器能可靠的分断断路器;当电源电压
低于欠压脱扣器额定工作电压的 35%时,欠压脱扣器能防
止断路器闭合;当电源电压高于欠压脱扣器额定工作电压
的 85%时,欠压脱扣器能保证断路器可靠闭合。
When power voltage declines to 70%~35% of the rated working
Voltage of undervoltage tripper, the undervoltage tripper can
reliably break the breaker up; when power voltage is lower than
the rated working voltage of undervoltage tripper by 35%, the
undervoltage tripper can prevent the breaker from closing; when
power voltage is higher than the rated working voltage of undervoltage tripper by 85%, the
undervoltage tripper can guarantee the reliable closure of breaker.
欠压脱扣器接线图
Wiring Diagram of Undervoltage
tripper