5.
接线方式(接线图)/ Wiring Method
表 10-1:400A 额定电流以下连接导线采用的截面积和相适应的额定电流见表
Table 10-1: Under the rated current of 400A, sectional areas of connecting wires and corresponding
rated current, see the following table
表 10-2:400A 额定电流以上连接导线采用的截面积和相适应的额定电流表
Table 10-2: When the rated current is 400A and above, sectional areas of connecting wires and
corresponding rated current, see the following table
注:1)同断路器的连接,按照《外形、安装尺寸及接线方式》选择适合的接线方式;
2)此尺寸的铜排不能与本体直接连接,需要选购联接排附件。
Notes: 1) Connect to the breaker, select proper wiring methods according to the Appearance, Installation
Dimensions and Wiring Methods;
2) The copper busbar in such dimensions can ’t be directly connected to the noumenon, connecting line
accessories shall be purchased.
图 10:进出线示意图
Fig.10: Diagram of ingoing and outgoing line
额定电流(A)
Rated
current
10
16、
20
25 32
40、
50
63
70、
80
90、
100
125 160
180、
200、
225
250 280
315、
350
400
导 线 截 面 积
( mm
2
)
Sectional
areas of the
wires
1.5 2.5 4
6
10
16 25
35
50
70
95
120 150 185
240
额定电流(A)
Rated current
电缆 Cables
铜排 Copper busbar
数量
Quantity
截面积(mm
2
)
Cross-section
数量
Quantity
尺寸
(mm)
Size
450、500
2
150
2
30³5
550、600、630
2
185
2
40³5
700、750、800
2
240
2
50³5