vertically, the angle of inclination between the installation surface and vertical surface shall
be ≤±22.5°.
图 14.1:垂直安装 图 14.2:水平安装
Fig.14.1 Vertical installation Fig.14.2 Horizontal installation
9.
使用和维护/ Application & Maintenance
9.1 欠压脱扣器 Under-voltage release
断路器带有欠压脱扣器时,应使欠电脱扣器先通电,断路器才允许合闸。
If the breaker has the Under-voltage release, the Under-voltage release should be electrified
before breakers can be closed.
(1)根据外挂欠电压模块上的接线端子编号接入电源(直流电源不必区分正负极)
。
(2)在额定控制电源电压的 35%-70%时,欠压脱扣器应可靠使断路器脱扣;
(3)在额定控制电源电压的 85%-110%时,欠压脱扣器应保证断路器能合闸;
(4)在额定控制电源电压低于 35%时,欠压脱扣器应防止断路器合闸。
(1)Power supply is connected to the release according to wiring terminal number of the add-on
Under-voltage module (no need to distinguish positive and negative for direct current).
(2)At rated control supply voltage of 35%-70%, Under-voltage release should be reliable to
trip breakers. (3)At rated control supply voltage of 85%-110%, Under-voltage release should
be able to close breakers.
(4)At rated control supply voltage less than 35%, Under-voltage release should prevent
breakers from
closing.
9.2 分励脱扣器 Shunt release
根据引出的导线编号接入电源(直流电源不必区分正负极)。当分励脱扣器的外加电压介于额定控制
电源电压的 70%-110% 之间时,能可靠分断断路器。
Power supply is connected to the shunt release according to outlet wire number (no need to
distinguish positive and negative for direct current). At rated control supply voltage of 70%-110%,
shunt release should be reliable to trip breakers.
图
15-1:欠压脱扣器接线图 图 15-2:分励脱扣器接线图
Fig.15-1 Wiring diagram of Under-voltage release Fig.15-2 Wiring diagram of
shunt release
9.3 辅助触头、报警触头 Auxiliary contact and alarm contact
9.3.1 辅助、报警触头接入相应外围控制电路 Peripheral control circuits of connection of auxiliary
and alarm contacts