9
TY-EJ15-003A Rev.2
3.2.2 Insulated barrier (Non-hazardous Area)
The following table shows the recommended insulated barriers (safety barriers) to be used
with the EJ15 pressure sensor. The insulation barrier does not require grounding regulated
for the intrinsically safe construction as it is isolated from the Intrinsically Safe Circuit.
Manufacturer
P&F Co., Ltd.
Cooper Industries
Japan K.K.
GM International
s.r.l
Model
KFD2-STC4-Ex1
MTL5541
D5014S
D5014D
Type approval No. (Japan)
No. TC16232
No. TC19435
No. TC21005
Explosion-proof construction
Exia IIC
Exia IIC
Exia IIC
Sa
fe
ty
h
o
ld
in
g
ra
tin
g
Maximum output voltage (Uo)
25.4 V
28 V
25.9 V
Maximum output current (lo)
86.8 mA
93 mA
92 mA
Maximum output power (Po)
551 mW
0.65 W
594 mW
Maximum external inductance (Lo)
4.6 mH
4.2 mH
3.0 mH
Maximum external capacitance (Co)
0.093 μF
0.083 μF
0.100 μF
Ambient temperature
60 degrees C
60 degrees C
70 degrees C
Load resistance in safe area
800Ω MAX.(20 mA DC)
450Ω MAX.(20 mA
DC)
550Ω MAX.(20 mA
DC)
* Safety barrier can be selected by the user.
3.2.3 Zener barrier (Non-hazardous Area)
The following table shows a recommended Zener barriers (safety barrier) to be used with
the EJ15 pressure sensor.
Manufacturer
Cooper Industries
Japan K.K.
Model
Type approval No. (Japan)
No. TC16447
Explosion-proof construction
Exia II C
Sa
fe
ty
h
o
ld
in
g
ra
tin
g
Maximum output voltage (Uo)
28 V
Maximum output current (lo)
93 mA
Maximum output power (Po)
0.65 W
Maximum external inductance (Lo)
3.05 mH
Maximum external capacitance (Co)
0.083 μF
Ambient temperature
60 degrees C
Load resistance in safe area
R
L
(Ω) = 50E - 900
* Safety barrier can be selected by users.
When you use a zener barrier, a single Class A grounding work is
required under the intrinsically safe regulations.
< Table 3-3 >
< Table 3-4 >