TY-KJ16-001A
16/25
9-3
.
System configuration
1. Isolated barrier
* 1: It is necessary to earth ground from the KJ16 main body (joint part), so please install it so that it is
grounded through piping.
In the unlikely event that earth grounding from piping is impossible, please use the
shielded wire to ground the earth. However, when both the KJ16 main body and the
shielded wire are grounded, please make one point ground so as not to generate a
potential difference.
2. Zener barrier
9-4
.
Connection layout
1. Isolated barrier
As shown in the wiring diagrams on the following pages, place the safety device (KJ 16) in
a hazardous place, securely hold the equipment (insulated barrier), general equipment
(supply power, receiver) in a non-hazardous place and connect .
In addition, when purchasing an insulated barrier, it is not necessary to singly provide
Class A grounding for intrinsic safety. For connection details and other details, please
refer to the product instruction manual purchased.