background image

Nailor Industries Inc. reserves the right to change any information concerning product or specification without notice or obligation.

Page 2.094

3/16  IOM-MBFDIMP

OPERATION AND MAINTENANCE PROCEDURES

MULTI-BLADE AND TRUE ROUND FIRE DAMPERS

MODEL SERIES: (D)1200(SS)(-3)(-OW)(-DOW), D1250

AND 1290F(-SS)

Dampers are an essential part of the fire protection system

in a building. The NFPA recommends that fire dampers be

tested periodically to verify the operational abilities of each

installed damper. See NFPA 80, 

Standard for Fire Doors

and  Other  Opening  Protectives

,  for  Operational  and

Periodic Inspection and Testing details. 

CAUTION:

High  torque  helical  spring  under  tension,  ensure  HVAC

fans  are  turned  off. Testing  spring  assisted  fire  dampers

under  airflow  conditions  is 

NOT  RECOMMENDED

and

may severely damage or destroy ductwork. Use protective

eyewear or safety glasses. Keep hands out of the blade

path,  as  this  can  cause  serious  injury.  Keep  any  hard

objects or tools out of the blade path as they can damage

the blades when closing. 

Releasing of the fusible link 

1. Using  a  suitable  heat  source,  apply  heat  at  a  slightly

higher temperature than the rating of the fusible link until

the link melts. When applying the heat to the fusible link

position the heat source in a manner so no heat is directed

towards the spring as the excessive heat can negatively

affect the spring performance. 

AS  SOON  AS  THE  LINK  HAS  MELTED,  THE 

SPRING  WILL  FORCE  THE  BLADES  TO  CLOSE

INSTANTANEOUSLY. THE BLADE PATH MUST BE

KEPT CLEAR.

Reloading the spring assembly 

2. Loosen  the  jackshaft  from  the  bolt  on  crank  arm

quadrant,  located  on  the  jackshaft  side  opposite  of  the

spring assembly 

(A)

. Do not remove the bolt completely.

See Detail 1.
3. Attach a pair of vise grips on the jackshaft 

(B)

and turn

upwards until the two pins on the spring assembly are at a

distance at which the new fusible link can be installed 

(C)

.

This is approximately 90° of rotation. See Detail 2.

Note:

On  smaller  size  dampers,  two  vise  grips  may  be

required to open the damper. Use one vice grip to open as

much as the duct free area will allow, then set the second

vise grips on the jackshaft per above. Unlock the first set of

vise grips, remove and  turn the second set upwards as

free area will allow. Repeat as necessary.
4. Place  the  new  fusible  link  over  the  two  pins  on  the

spring assembly (making sure temperature rating is visible)

and locate in the pin grooves 

(C)

. See Detail 2. 

Required Items:

(1) Protective eyewear or safety glasses
(1) Pair of work gloves 
(1) Suitable heat source
(2) Vise grips
(1) 1/2" (13) wrench
(1) Needle nose pliers
(1) Replacement "Globe" Fusible link per damper section, 

of the same temperature rating as the original link. 

Detail 1

Detail 2

Page 1 of 2

Summary of Contents for 1290F

Page 1: ...inkage Jackshaft to blade Bearings 1 2 13 dia self lubricating oilite bronze Axles 1 2 13 dia plated steel double bolted to blades Jackshaft 1 2 13 dia cadmium plated steel Supplied with factory mounted hand locking quadrant Fusible Link 165 F 74 C standard 212 F 100 C available Sizes Duct Dia Note Dampers available in 1 25 increments Vertical or horizontal installation OPTIONS BS Stainless steel ...

Page 2: ...eel jackshaft to blade Bearings 1 2 13 dia stainless steel Axles 1 2 13 dia stainless steel double bolted to blades Jackshaft 1 2 13 dia stainless steel Supplied with factory mounted hand locking quadrant Fusible Link 165 F 74 C standard 212 F 100 C available Sizes Duct Dia Note Dampers available in 1 25 increments Vertical or horizontal installation CONSTRUCTION TYPE 304 Type 304 Stainless Steel ...

Page 3: ...0 Vdc Standard Mounting MS1 is damper open signal MS2 is damper closed signal Non Standard Mounting Important Installer must double check continuity of MS1 and MS2 before wiring to determine which switch signals the damper s open or closed position EXTERNAL RIGHT HAND MOUNTING FRONT VIEW LESS COVER COVER A A 2 7 8 73 3 76 4 1 8 105 MS 2 MS 1 BLUE YELLOW SECTION A A JACKSHAFT DRIVESHAFT EXTENSION C...

Page 4: ...0 94 100 47 400 189 01 3 2 50 02 5 03 8 1 25 15 37 04 10 08 20 05 13 06 15 7 174 6 5 150 125 4 100 3 75 25 62 PRESSURE DROP Pressure Drop tested per AMCA Standard 500 D Fig 5 5 PERFORMANCE DATA MODEL SERIES 1290F 1 1 2 HOUR LABEL AND 1290F SS 1 1 2 HOUR LABEL 1290F Maximum Performance Ratings UL 555 Fire Rating 1 1 2 Hour Maximum Velocity 2000 fpm 10 m s Maximum Pressure 4 in w g 1 kPa 1290F SS Ma...

Page 5: ...steel 1290F or stainless steel 1290F SS 4 Splice clips 20 gauge 1 0 galvanized steel 1290F or stainless steel 1290F SS two pairs for each plate 5 Steel or wood runner 6 Retaining clip 1 x 1 x 1 25 x 25 x 25 20 gauge 1 0 galvanized steel 1290F or stainless steel 1290F SS angle see note 5 7 10 sheet metal screw 8 1 8 3 dia steel pop rivet or 10 x 1 2 13 sheet metal screws or tack or spot welds 9 1 4...

Page 6: ...ngage metal or wood studs or runners On masonry installations the damper plate shown in Fig 3 should be used This has four equally spaced clips 1 x 1 x 1 25 x 25 x 25 20 gauge 1 0 which are attached to the plate and damper sleeve using 3 16 5 rivets tack or spotwelds Make sure that fasteners do not interfere with the operation of the damper blade For dampers 12 305 dia or less single side retainin...

Page 7: ...at source in a manner so no heat is directed towards the spring as the excessive heat can negatively affect the spring performance AS SOON AS THE LINK HAS MELTED THE SPRING WILL FORCE THE BLADES TO CLOSE INSTANTANEOUSLY THE BLADE PATH MUST BE KEPT CLEAR Reloading the spring assembly 2 Loosen the jackshaft from the bolt on crank arm quadrant located on the jackshaft side opposite of the spring asse...

Page 8: ...ove any obstructions dirt rust corrosion or other observed conditions that could impede proper damper operation Clean damper blades and other moving parts if necessary Use of a mild detergent or solvents is recommended for any cleaning required 2 Check closure springs If damaged or defective repair or replace 3 Linkage and jackshaft bearing brackets should be lubricated with a dry lubricant such a...

Page 9: ...ire smoke and smoke dampers Position Indicator Microswitch Data Switch Type Single Pole double throw 2 15 Amps 1 3 HP 125 250 Vac or 24 Vdc 1 2 Amp 125 Vdc 1 4 Amp 250 Vdc EXTERNAL RIGHT HAND MOUNTING FRONT VIEW LESS COVER COVER A A 2 7 8 73 3 76 4 1 8 105 MS 2 MS 1 BLUE YELLOW SECTION A A JACKSHAFT DRIVESHAFT EXTENSION CONDUIT CONNECTION DUCT OR SLEEVE 13 16 21 JACKSHAFT MOUNTING BRACKET 1 6 7 5 ...

Page 10: ... actuator MS1 is damper open signal MS2 is damper closed signal Important Installer must double check continuity of MS1 and MS2 before wiring to confirm which switch signals the damper s open or closed position 2 Connect external wiring and electrical power supply 120 or 24 Vac in accordance with N E C and any applicable local codes 3 Replace junction box cover and check operation L2 L1 CLOSED RED...

Reviews: