Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
W
15 1/2" (394)
14" (356)
5 3/4"
(146)
5 3/4"
(146)
5 1/2"
(140)
1/2"
(13)
H
UNIVERSAL PNEUMATIC
CONTROL MOUNTING
PANEL AND PROTECTIVE
SHROUD
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
MULTI-POINT
AVERAGING
FLOW SENSOR
W
1/2"
(13)
H
SLIP AND DRIVE CONNECTION
OPTIONAL
ACCESS DOOR
AIRFLOW
D AMPER
DRIVESHAFT
6 1/2"
(165)
DATE
B SERIES
SUPERSEDES DRAWING NO.
3 - 12 - 18
3000
8 - 3 - 08
P3001-1
Page 1 of 2.
Dimensions are in inches (mm).
SINGLE DUCT TERMINAL UNIT
PNEUMATIC CONTROLS • PRESSURE INDEPENDENT
VARIABLE OR CONSTANT VOLUME
MODEL: P3001
Dimensional Data
Unit
Size
Airflow Range
*
cfm (l/s)
W
H
Inlet Size
4
5
6
0 – 180 (0 – 85)
0 – 325 (0 – 153)
0 – 450 (0 – 212)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
10 (254)
3 7/8 (98) Round
4 7/8 (124) Round
5 7/8 (149) Round
7
8
9
0 – 650 (0 – 307)
0 – 900 (0 – 425)
0 – 1150 (0 – 543)
12 (305)
12 (305)
14 (356)
12 1/2 (318)
12 1/2 (318)
12 1/2 (318)
6 7/8 (175) Round
7 7/8 (200) Round
8 7/8 (225) Round
10
12
14
0 – 1500 (0 – 708)
0 – 2050 (0 – 967)
0 – 2550 (0 – 1203)
14 (356)
18 (457)
24 (610)
12 1/2 (318)
12 1/2 (318)
12 1/2 (318)
9 7/8 (251) Round
12 15/16 x 9 13/16 (329 x 249) Oval
16 1/16 x 9 13/16 (408 x 249) Oval
16
24 x 16
0 – 3040 (0 – 1435)
0 – 6800 (0 – 3209)
28 (711)
38 (965)
12 1/2 (318)
18 (457)
19 3/16 x 9 13/16 (487 x 249) Oval
23 7/8 x 15 7/8 (606 x 403) Rect.
Standard Features:
• 22 ga. (0.86) zinc coated steel casing,
mechanically sealed, low leakage
construction.
• 16 ga. (1.63) corrosion-resistant steel
inclined opposed blade damper with
extruded PVC seals (single blade on
size 4, 5, 6). 45° rotation, CW to close.
Tight close-off. Damper leakage is less
than 2% of the terminal rated airflow at
3" w.g. (750 Pa).
• 1/2" (13) dia. plated steel drive shaft.
An indicator mark on the end of the shaft
shows damper position.
• Multi-point averaging Diamond Flow
Sensor. Aluminum construction. Supplied
with balancing tees.
• Rectangular discharge with slip and
drive cleat duct connection.
• Full NEMA 1 type controls enclosure for
factory mounted controls.
• 3/4" (19), dual density insulation,
exposed edges coated to prevent air
erosion. Meets the requirements of
NFPA 90A and UL 181.
• Right-hand controls location is standard
(shown) when looking in direction of
airflow. Optional left hand controls
mounting is available.
Controls:
q
By Nailor (See seperate submittal).
q
By Others.
Options and Accessories:
q
Steri-liner.
q
Fiber-free liner.
q
Solid metal liner.
q
Perforated Metal Liner.
q
1" (25) liner.
q
Bottom access door.
q
Hanger brackets.
q
20 ga. (1.00) construction.
q
Protective controls shroud cover.
Seismic Certification:
q
SSI (Standard)
q
OSHPD
q
Special Features: _____________ .
*
Maximum airflow limit is based upon 1.0" w.g. (249 Pa) max. differential pressure signal from
Diamond Flow Sensor.
Listed