Nailor Industries Inc. reserves the right to change any information concerning product or pricing without notice.
SCHEDULE TYPE:
PROJECT:
ENGINEER:
CONTRACTOR:
DATE
B SERIES
SUPERSEDES DRAWING NO.
3 - 12 - 18
3000
10 - 28 - 16
D3001Q
Page 1 of 1.
Dimensions are in inches (mm).
SINGLE DUCT TERMINAL UNIT WITH
DISSIPATIVE SILENCER • SUPER QUIET
DIGITAL CONTROLS • VARIABLE OR CONSTANT VOLUME
MODEL: D3001Q
Standard Features:
• Designed for noise sensitive applications
such as classrooms, libraries, studios and
performance halls.
• 22 ga. (0.86) zinc coated steel casing,
mechanically sealed, low leakage
construction.
• 16 ga. (1.63) corrosion-resistant steel
inclined opposed blade damper with
extruded PVC seals (single blade on size
4, 5, 6). 45
°
rotation, CW to close. Tight
close-off. Damper leakage is less than
2% of the terminal rated airflow at 3" w.g.
(750 Pa).
• 1/2" (13) dia. plated steel drive shaft.
An indicator mark on the end of the shaft
shows damper position.
• Multi-point averaging Diamond Flow
Sensor. Aluminum construction. Supplied
with balancing tees.
• Rectangular discharge with slip and
drive cleat duct connection.
• Full NEMA 1 type controls enclosure for
factory mounted controls.
• VAV section is lined with 3/4" (19),
dual density insulation, exposed edges
coated to prevent air erosion. Meets the
requirements of NFPA 90A and UL 181.
• Right-hand controls location is standard
(shown) when looking in direction of
airflow. Optional left hand controls
mounting is available.
Silencer Section:
• Designed to mate w/VAV section for
optimum performance and super quiet
operation.
•
Optimized internal baffle geometry
reduces self-generated noise, minimizes
pressure drop and maximizes acoustic
attenuation.
• 22 ga. (0.86) coated steel perforated
baffles encapsulate fiberglass acoustic
media.
• Internal insulation on top and bottom
exposed panels optimizes sound
reduction and eliminates need for external
field applied thermal duct wrap.
Digital Controls:
q
Nailor EZvav (See separate submittal).
q
Factory mount (by others).
q
Field mount.
Options and Accessories:
q
24 VAC control transformer.
q
Bottom access door.
q
Controls enclosure for field mounted
controls.
q
Dust tight enclosure seal.
q
FMI Removable insert type Diamond
Flow Sensor.
q
Hanger brackets.
q
Toggle disconnect switch.
Seismic Certification:
q
SSI (Standard)
q
OSHPD
q
Special Features: _______________ .
Terminal Unit Liner:
q
Fiber-free liner.
q
Perforated metal liner.
q
Solid metal liner.
q
Steri-liner.
q
Steri-liner + Perforated metal liner.
Silencer Acoustic Media:
q
Fiberglass Cloth liner.
q
Mylar/Spacer liner.
5 1/2"
(140)
W
1/2"
(13)
H
W
6"
(152)
1/2"
(13)
H
15 1/2" (394)
51 1/2" (1308)
14" (356)
36" (914)
RECTANGULAR
DISSIPATIVE SILENCER
SLIP AND DRIVE
CONNECTION
AIRFLOW
6"
(152)
OPTIONAL
ACCESS DOOR
DAMPER
DRIVESHAFT
OPTIONAL
(FMI)
REMOVABLE
FLOW SENSOR
CONTROLS ENCLOSURE
FOR FACTORY MOUNTED
CONTROLS
INLET: ROUND,
FLAT OVAL OR
RECTANGULAR
MULTI-POINT
AVERAGING
FLOW SENSOR
11"
(279)
*
Maximum airflow limit is based upon 1.5" w.g. (373 Pa) max. differential pressure signal from Diamond Flow Sensor.
Unit
Size
Airflow Range*
cfm (I/s)
W
H
Inlet Size
4
0 – 225 (0 – 106)
10 (254)
10 (254)
3 7/8 (98) Round
5
0 – 400 (0 – 189)
10 (254)
10 (254)
4 7/8 (124) Round
6
0 – 550 (0 – 260)
10 (254)
10 (254)
5 7/8 (149) Round
7
0 – 800 (0 – 378)
12 (305)
12 1/2 (318)
6 7/8 (175) Round
8
0 – 1100 (0 – 519)
12 (305)
12 1/2 (318)
7 7/8 (200) Round
9
0 – 1400 (0 – 661)
14 (356)
12 1/2 (318)
8 7/8 (225) Round
10
0 – 1840 (0 – 868)
14 (356)
12 1/2 (318)
9 7/8 (251) Round
12
0 – 2500 (0 – 1180)
18 (457)
12 1/2 (318)
12 15/16 x 9 13/16 (329 x 249) Oval
14
0 – 3125 (0 – 1475)
24 (610)
12 1/2 (318)
16 1/16 x 9 13/16 (408 x 249) Oval
16
0 – 3725 (0 – 1758)
28 (711)
12 1/2 (318)
19 3/16 x 9 13/16 (487 x 249) Oval
24 x 16
0 – 8330 (0 – 3931)
38 (965)
18 (457)
23 7/8 x 15 7/8 (606 x 403) Rect.
Dimensional Data
Listed