OPERATION AND USERS INSTRUCTIONS
ACN ANALOG THERMOSTAT (CTE-5201)
FAN COIL UNITS

Engineered Comfort reserves the right to change any information concerning product or specification without notice or obligation.

Page 1 of 2

2/14/11  EC-IOM-ACN

Model CTE-5201W16 Thermostat:

Model CTE-5201-16 (LCD analog thermostat) (Figure 2) - single
output  with  limits,  PI  function  is  designed  to  be  used  with  the
CEE-5201 Fan Coil Unit controller (Figure 1). Model CTE-5201-16
Thermostat comes with the following factory default settings:

Set Point (Default):

70°F

MAX:

100%

MIN:

20%

F/C Mode:

Degrees F

UNOCC Mode:

OFF

PROP:

4ºF

INT:

30 Minutes

To  change  any  one  of  these  values,  except  the  F/C  Mode,  first
push the button to display the value to be changed.  Use the Up /
Down  buttons  to  change  the  value.    Then  hold  down  the
corresponding button for approximately 10 seconds until the display
begins to flash. The new value has now been written into memory.
To  change  to  degrees  C  mode  simply  press  and  hold  the  F/C
button  down  for  10  seconds  until  the  display  begins  to  flash. To
change back to degrees F repeat the procedure.

Set Point (Normal)

The set point range is 60 – 85°F (15.6 – 29.4°C).  To change the
set point, push the SET POINT button to display the current value.
Use the Up / Down buttons to change the value.  The display will
time out and revert back to displaying the room temperature and
the thermostat will control to the new set point.

Set Point (Default)

If power is lost, when the unit is powered back up, the set point will
revert to the default value of 70°F (21.1 C).  This default value can
be  changed  to  any  value  in  the  set  point  range. This  default  set
point is also used in the dead band unoccupied mode.

MAX

This  is  the  maximum  value  that  the  output  can  attain.  It  is
adjustable up to 100% (10 volts) and down to the MIN setting.

MIN

This  is  the  min.  value  that  the  output  can  attain.  It  is  adjustable
down to 0% (0 volts) and up to whatever the MAX is set for.

F/C Mode

The  F/C  button  toggles  the  display  between  °F  and  °C.  Room
temperature, set point, proportional band, dead band, and offset
will be displayed in the desired units.  

UNOCC

Momentarily  pressing  this  button  will  put  the  unit  into  the
unoccupied mode. It will stay in this mode until either the Set Point
or  Up  /  Down  buttons  are  pushed.  There  are  two  unoccupied
modes, OFF or DEADBAND.

OFF UNOCC Mode

The output voltage is forced to 0 volts (0%). A safety override will
bring the output up to 2 volts placing the unit in heating if the room
temperature  falls  below  50°F.  The  output  will  return  to  0  volts
when the room temperature reaches 55°F.

DEADBAND UNOCC Mode

In  this  mode  the  set  point  is  set  to  70°F,  the  integral  action  is
disabled, and a dead band of +/- 10°F is set around the set point.
As long as the room temperature is within the dead band the fan

will run at MIN conditions.

PROP

The  proportional  band  is  the  temperature  band  around  the  set
point over which the output will vary from MIN to MAX due to the
proportional action alone. The proportional band is adjustable from
2 – 6°F (1.1 – 3.3°C).

INT

As  long  as  there  is  a  difference  between  room  temperature  and
set point, the integral action will cause the output to integrate up
or down. The integral time is the time it takes the integral action to
repeat  the  effect  of  the  proportional  action.    The  integral  time  is
adjustable from 15 to 30 minutes.  Setting the integral time to 0 will
disable the integral action.

Temperature Offset

By pressing both MIN and INT together it is possible to offset the
internal temperature sensor by +/- 2°F (+/- 1.1°C).  After using the
Up  /  Down  buttons  to  change  the  offset  both  the  MIN  and  INT
buttons  must  be  held  down  together  for  10  seconds  until  the
display begins to flash in order to write the new offset into memory.

Figure 1. 

CEE-5201 Analog Controller Card

Supply Voltage:

24 VAC +20/-15% 50/50Hz

Supply Power:

1 VA plus output loads

Discharge Temp Input:

10K OHM@25ºC, NTC 4.37% / ºC

Fan Output:

Min Adjustable 0–10 VDC
Stage 1 Max adjustable from Min to 10 VDC
Stage 2 Max adjustable from stage 1 Max to  10VDC
Cooling Max adjustable from Min to 10 VDC

CWV Output:

Max adjustable from 0 to 10 VDC

Heat Stage 1 & 2 Outputs:

Triac outputs 10VA Max @ 24VAC

Thermostat connector:

PIN 1 NC
PIN 2 DC COM
PIN 3 Supply Output 16 VDC +/-10% 10mA
PIN 4 Tin 1-10 VDC 100 KOHM
PIN 5 DC COM
PIN 6 NC

Connections:

Plated screw terminals 14 to 22 AWG Cu
RJ-11 thermostat jack

Ambient Limits: 

Operating 0 to 120ºF (-18 to 49ºC)
Shipping -40 to 140ºF (-40 to 60ºC)

Mounting:

Open Board / Snaptrack supplied