2/14/11 EC-IOM-ACN
Page 2 of 2
F a n C o i l U n i t s
www.engineered-comfort.com
Supply Voltage:
14 -19 VDC
Set Point Range:
60 – 85°F (15.6 – 29.4°C)
(Power On Default: 70°F / 21.1°C)
Temperature Sensor Type:
Thermistor
Accuracy:
+/- 0.36–F (0.2°C)
Display Degrees F or C:
Selectable (Factory Setting: Degrees F)
Direct Acting Output:
0 – 10 VDC
MIN / MAX Limits:
Adjustable 0 – 100%
(Factory Settings: MIN=20, MAX =100)
Proportional Band:
2 – 6°F (1.1 – 3.3°C) (Factory Setting: 4°F)
Integration Time:
15 – 60 Minutes (0=OFF)
(Factory Setting: 30)
Unoccupied Setpoint Modes:
OFF or Deadband
(Factory Setting: OFF)
OFF Mode:
Output Voltage = 0.0 Volts
(Safety Override: Output Cycles 0.0 Volts to
2.0 Volts. To Maintain 50°F to 55°F)
Deadband Mode:
Integral Action Disabled & Set Point.
Set to D/- 10°F Deadband.
Deadband Output Midway between Max &
Min
.
Temperature Offset:
Adju/-2°F (+/- 1.1°C)
(Press MIN & INT together)
Operating Ambient:
34 – 125°F (1.1 – 51.6°C)
Shipping Ambient:
-40 – 140°F (-40 – 60°C)
Humidity:
0 – 95% Non Condensing
Case Material:
White ABS.
UL Frame Class 94HB.
RJ-11 Female Connector.
PIN1 NC PIN2 COM PIN3 SUPPLY
PIN4 OUT PIN5 COM PIN6 NC
3 1/8" (79)
5"
(127)
7/8"
(22)
3/8"
(10)
SETPOINT
ROOM TEMP
VIEW WITH COVER OPENED
SET
POINT
SET
POINT
DOWN BUTTON
UP BUTTON
SET POINT
BUTTON
MAX
F/C
PROG
MIN
UNOCC
INT
ACCESSORIES
HMO-1161W:
4" x 4" wallplate, White
HPO-0044:
Replacement allen screws
HSO-5013-50:
50' plenum cable w/conn.
HSO-5013-03:
3' plenum cable w/conn.
THERMOSTAT TO BASE
MOUNTING SCREWS (2)
(1/16" ALLEN SOCKET)
TURN IN TO REMOVE
THERMOSTAT FROM BASE
PIN1
PIN6
3 1/4"
(83)
2 4/7"
(65)
ø
.15
Figure 2.
Model CTE-5201W16 (Fan Coil Unit LCD analog thermostat)
Calgary, Canada
Tel: 403-279-8619
Fax: 403-279-5035
Houston, Texas
Tel: 281-590-1172
Fax: 281-590-3086
Toronto, Canada
Tel: 416-744-3300
Fax: 416-744-3360
Las Vegas, Nevada
Tel: 702-648-5400
Fax: 702-638-0400
All manuals and user guides at all-guides.com