Outline
TMR: Sets the ON-delay timer for 0.01 s units (0 to 327.67 s)
TMX: Sets the ON-delay timer for 0.1 s units (0 to 3276.7 s)
TMY: Sets the ON-delay timer for 1 s units (0 to 32767 s)
Program example
■
Operands
■
Explanation of example
■
Time chart
ON
OFF
X0
ON
OFF
T5
ON
OFF
Y0
3s
3s
• Three seconds after X0 turns ON, timer contact T5
turns ON. Then Y0 goes ON.
Timer/Counter
area
EV
Relay
SV
WR
WY
WX
Instruction
Set value
N/A N/A N/A
A
N/A
A:
N/A: Not Available
Register
DT
N/A
IY
IX
N/A N/A
H
K
A
N/A
Constant
Index
modifier
N/A
Index
register
Available
5-3. Description of Basic Instructions
TMR
0.01s units timer
TMX
0.1s units timer
TMY
1s units timer
Ladder Diagram
FP Programmer
II
key operations
Boolean Non-ladder
Address Instruction
0
X0
T5
Set value
Timer instruction
number
5
Y0
TM X 30
4
ST
X-WX
TM
T-SV
ENT
5
ST
X-WX
ST
X-WX
0
WRT
OT
L-WL
AN
Y-WY
0
WRT
(BIN)
K/H
0
WRT
TM
T-SV
ST
X-WX
WRT
5
WRT
3
0
1
4
5
ST
X
0
TM
X
5
K
30
ST
T
5
OT
Y
0
Availability
Step
3
3
4
All series
Timer instruction number
C14 and C16 series:
up to 128
C24, C40, C56, and C72 series: up to 144
The number of the
TM
instructions is shared with that of the
CT
instructions.
You can change the sharing of
TM
and
CT
instructions through the system
registers.
The default value of the
TM
and
CT
instruction is,
for C14 and C16 series:
TM
instruction: 0 to 99,
CT
instruction: 100 to 127
for C24, C40, C56, and C72 series:
TM
instruction: 0 to 99,
CT
instruction: 100 to 143
Set value
Range: K0 to K32767
Decimal constant or timer set value area (SVn)* whose number is same as its
timer instruction number (n)
*
“
SVn” can be specified only when the version of the CPU is 2.7 or later.
115
Summary of Contents for FP1
Page 1: ...PROGRAMMABLE CONTROLLER FP1 is a global brand name of Matsushita Electric Works Hardware ...
Page 28: ...20 ...
Page 98: ...90 ...
Page 150: ...142 ...
Page 208: ...200 ...
Page 226: ...218 ...
Page 280: ...272 ...