6-3. Description of High-level Instructions
Outline
Copies the hexadecimal digits in one 16-bit area to the specified digit in
another 16-bit area.
Program example
■
Operands
■
Explanation of example
• The hexadecimal digit 0 of the data register DT100 is copied to hexadecimal digit 0 of word external output relay
WY0 when trigger X0 turns ON.
n: H0
Bit position
DT100
0 0 0 0
0 0 0 1
11
8
0 1 0 0
1 0 0 1
3
0
Source [S]: H149
X0: ON
15
•
•
12
•
•
•
•
7
4
•
•
Hexadecimal
digit position
3
2
1
0
Bit position
WY0
0 0 0 0
1 0 0 0
11
8
1 0 1 0
1 0 0 1
3
0
Destination [D]: H8A9
15
•
•
12
•
•
•
•
7
4
•
•
Hexadecimal
digit position
3
2
1
0
In this case, only the lower 4 bits of WY0 change value.
"
"
"
"
"
Timer/Counter
EV
Relay
SV
WR
WY
WX
Operand
S
A
A
A
A
A:
N/A: Not Available
Register
DT
A
IY
IX
A
A
H
K
A
A
Constant
Index
modifier
A
Index
register
Available
A
n
A
A
A
A
A
A
A
A
A
A
A
N/A A
A
A
A
A
A
N/A N/A
A
A
D
F6
(DGT)
Hexadecimal digit move
Availability
Step
7
All series
S
n
D
16-bit equivalent constant or 16-bit area (source)
16-bit equivalent constant or 16-bit area (specifies source and destination
hexadecimal digit position and number of hexadecimal digits)
16-bit area (destination)
Ladder Diagram
Boolean Non-ladder
Address Instruction
10
X0
F6 DGT , DT100 , H0 , WY0
S
D
Trigger
n
10
11
ST
X
0
F 6 (DGT)
DT
100
H
0
WY
0
162
Summary of Contents for FP1