202
7-1. Self-diagnostic Function
7-1. Self-diagnostic Function
FP1 programmable controllers use the self-diagnostic function when something goes wrong with the FP1.
The abnormalities detected by the self-diagnostic function are divided into three categories:
• Self-diagnostic error
This type of error is detected when the following occurs:
- Hardware problem in CPU or ROM, and backup battery problem. (ROM, system, interrupt, or battery abnormality)
- An instruction is incorrectly executed in RUN mode (operation error).
• Total-check error
This type of error is detected by a total-check operation when the following occurs. The total-check operation is
performed when the mode selector is changed from PROG. to RUN.
- Program abnormalities such as syntax errors, duplicated use of output, and instruction combination errors.
(syntax error, duplicated output error, not paired error, mismatch error, program area error, operand error)
The total-check operation can also be performed by using the FP Programmer II (OP9 function) or the NPST-GR
Software [“1.TOTALLY CHECK A PROGRAM” (menu 1) or “V.TOTALLY CHECK” (menu 2)].
• System watchdog timer error
This type of error is detected when the following occurs:
- program scan time is extraordinarily long
- hardware abnormality is detected
1. Operation Monitor LEDs When an Error Occurs
Content
Normal operation
Forcing ON/OFF
RUN
PROG.
RUN
PROG.
RUN
PROG.
RUN
PROG.
RUN
PROG.
RUN
ON
OFF
Flash
OFF
Varies
OFF
OFF
OFF
Varies
Varies
PROG.
OFF
ON
OFF
ON
Varies
ON
ON
ON
Varies
Varies
ERR.
OFF
OFF
Varies
Varies
ON
ON
ON
OFF
Varies
Varies
ALARM
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
Position of the
Mode Selector
When a self-diagnostic
error occurred
When a total-check error
occurred
When a system watchdog
timer error occurred
LED status
COM
0
COM
1
2
100 240 V AC
F.G.
RUN
REMOTE
PROG.
RUN
PROG.
ERR.
ALARM
BATTERY
0
1
OUTPUT
Y
(24V DC)
Operation Monitor LEDs
Mode Selector
The status of the Operation Monitor LEDs on the
Control Unit vary, as shown in the table below.
Summary of Contents for FP1
Page 1: ...PROGRAMMABLE CONTROLLER FP1 is a global brand name of Matsushita Electric Works Hardware ...
Page 28: ...20 ...
Page 98: ...90 ...
Page 150: ...142 ...
Page 208: ...200 ...
Page 226: ...218 ...
Page 280: ...272 ...